Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop E
Sequence Number 4
Notes
Date Text
2005-06-22 00:00:00********** REVSIONS UNSAT **********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW. INFORMATION FOR GENERATOR, ATS,
 FIRE PUMP, FUEL TANK ETC WAS NOT
 SUBMITTED UNDER MAIN PERMIT A "PROVISO"
 WAS GIVEN IN ORDER TO ISSUE BLDG PERMIT.
 PLEASE NOTE:GEN, FIRE PUMP ETC IS ALL
 REQUIRED TO BE SUBMITTED UNDER SEPARATE
 PERMIT(S) AND SEPARATE PERMIT FEES WILL
 APPLY.
 AS OF THIS REVIEW, NO PERMIT APPLICATION
 HAS BEEN SUBMITTED.
  
 2)NOTE: PLEASE SEE ALL FEEDERS ETC WHICH
 HAVE NOW BEEN CHANGED TO "ALUM".
 PLEASE SEE PER LOCAL AMENDMENTS, NO ALUM
 FOR GROUNDING OR BONDING IS PERMITTED.
 PLEASE REMOVE ALUM NOW SHOWN FOR THIS.
 PLEASE ALSO SEE NO ALUM IS PERMITTED
 SMALLER THAN #2.
 PLEASE NOW SPECIFY ON PLANS EACH FEEDER
 ETC WHICH WILL BE ALUM AND WHICH WILL BE
 COPPER AS SOME ARE NOT SPECIFIED.
 ORIG PLANS INDICATED ALL CONDUCTORS WERE
 TO REMAIN COPPER AND NO ALUM WAS TO BE
 INSTALLED PER ENGINEER.
 310.2,250.62
 PLEASE ALSO SEE NEXT NOTE FOR MIN
 SIZING.
  
 3)NOTE: PLEASE SEE 240.4C WHERE THE
 OVERCURRENT DEVICE IS RATED OVER 800
 AMPERES, THE AMPACITY OF THE CONDUCTORS
 IT PROTECTS SHALL BE EQUAL TO OR GREATER
 THAN THE RATING OF THE OVERCURRENT
 DEVICE DEFINED IN 240.6.
  
 NEW NOTES NOT ON ORIG REVIEW.
  
 1)NOTE; PLEASE SEE ALTERNATING OF EM
 CIRCUITS IN HALLWAY, AGRESS AREAS WILL
 BE REQUIRED. THESE AREAS ARE TO BE
 CIRCUITED AS STAIR-WELLS WHICH ARE SHOWN
 WITH ALTERNATING CIRCUITS. NFPA 101 7-9
  
 2)NOTE: PLEASE SEE MIN CIRCUITING
 REQUIRED FOR ELEVATOR MACHINE RMS PER
 620.23,620.24. MIN CIRCUITING REQUIRED
 NOT TO BE PART OR SHARE OTHER AREAS.
  
 3)NOTE: PLEASE SEE MANY UNITS WHICH
 INDICATE GEN LT /RECEPTS CIRCUITS SHOWN
 IN DINING/ KITCHEN AREAS. B1,B2,B3,B4
 ETC,PH3, PH9 ETC.
 PLEASE SEE GEN LT CIRCUIT IN KITCHEN.
 210.52B1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  