2004-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 CITY WPB CODE
  
 1) FROM PREVIOUS REVIEW: (15)
 SHT P4.12 DETAIL #2 DOES NOT REFLECT THE
 FLOOR PLAN AT SECOND BATHROOM (ROOM 119)
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM (ROOM 119)
 2) SHT P4.14 STORM DRAIN COLLECTION ISO.
 SHOW THE FIRE STANDPIPE DRAINING IN THE
 STORY WATER SYSTEM. THIS IS NOT APPROVED
 PER CITY CODE SECTION 90-203(A). FIRE
 STANDPIPE DRAIN SHALL CONNECT INDIRECTLY
 TO SANITARY.
 3) ALL AERATORS AND DEAERATORS SHALL
 MEET THE STANDARDS AND SPECIFICATIONS OF
 ASTM A74-98 & A888-98 ASTM AND 301-97
 CISPI. SUBMIT INFORMATION SHOWING FITT-
 INGS HAVE MET THESE STANDARDS AS INDICA-
 TED BY A RECOGNIZED TESTING AGENCY.
 CHAPTER 14 FBC-2001.
  