| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-09-17 00:00:00 | DENIED: | | | REFERENCE RESPONSE LETTER DATED AUGUST | | | 12, 2004: | | | RESPONSE #2, FIRE DAMPER REMOVED FROM | | | GENERATOR EXHAUST.OPENINGS ON THE | | | EXTERIOR WALL ARE TO BE PROTECTED.THE | | | ORIGINAL COMMENT DID NOT STATE THAT A | | | FIRE DAMPER COULD NOT BE ON THE | | | GENERATOR BUT ASKED FOR THE MANUFACTURER | | | SUBMITTAL FOR THIS APPLICATION. | | | | | | PLEASE CLARIFY COMMENT ON PLAN SHEET | | | M8.01. GARAGE WILL NOT BE A PART OF THE | | | SMOKE CONTROL SYSTEM, THEREFOR WILL NOT | | | BE TIED INTO THE EMERGENCY POWER.HOW | | | WILL THE GARAGE COMPLY WITH THE | | | REQUIREMENT FOR VENTILATION AS PER | | | 2001 FBC(M) 403.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|