Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop M
Sequence Number 3
Notes
Date Text
2004-09-17 00:00:00DENIED:
 REFERENCE RESPONSE LETTER DATED AUGUST
 12, 2004:
 RESPONSE #2, FIRE DAMPER REMOVED FROM
 GENERATOR EXHAUST.OPENINGS ON THE
 EXTERIOR WALL ARE TO BE PROTECTED.THE
 ORIGINAL COMMENT DID NOT STATE THAT A
 FIRE DAMPER COULD NOT BE ON THE
 GENERATOR BUT ASKED FOR THE MANUFACTURER
 SUBMITTAL FOR THIS APPLICATION.
  
 PLEASE CLARIFY COMMENT ON PLAN SHEET
 M8.01. GARAGE WILL NOT BE A PART OF THE
 SMOKE CONTROL SYSTEM, THEREFOR WILL NOT
 BE TIED INTO THE EMERGENCY POWER.HOW
 WILL THE GARAGE COMPLY WITH THE
 REQUIREMENT FOR VENTILATION AS PER
 2001 FBC(M) 403.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.