| 2008-01-03 13:34:08 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | **PREVIOUS REVIEW COMMENTS** |
| | |
| | 1. **COMMENT NOT ADDRESSED** |
| | SHEET P4.16 SHOW THE LENGTHS OF PIPE FROM THE METER TO |
| | THE FIRST 8'-0" RISER AND SHOW THE LENGTHS OF PIPE FROM |
| | THE 200'-0" TO THE REGULATOR DOWNSTREAM OF ITEM (A). SO |
| | THE TOTAL DEVELOPED LENGTH CAN BE VERIFIED. |
| | |
| | 2. SHEET P4.16 SUBMIT THE COMPUTATIONS FOR THE |
| | EQUATION USED TO SIZE THE PIPE PER SECTION 402.3(2) SO |
| | THAT ALL FIGURES AND OUT COME CAN BE VERIFIED BY AN |
| | INDEPENDENT ENGINEER. |
| | **THE RESUBMITTED PLANS WITH THE CALCULATION "MAXIMUM |
| | ALLOWABLE PRESSURE DROP 1.5 PSI (42"W.C.)" IS WRONG |
| | WHERE THE "SECTION (FEET)" IS. THE INDICATED 237' |
| | MEASUREMENT INDICATED PER THE INDICATED CORRESPONDING |
| | LENGTHSOF CUT SECTIONS OF PIPE IS WRONG THAT SECTION |
| | OF PIPING PER THE INDICATED CORRESPONDING LENGTHS IS |
| | 267' WITH A PD OF 38.982. HOWEVER UNTIL COMMENT #1 IS |
| | ADDRESSED AND THE PLANS ARE CORRELATED THIS COMPUTATION |
| | CAN NOT PASS. CAN THESE ALLOWABLE PRESSURE DROPS BE |
| | DONE IN SECTIONS AS INDICATED ON THE PLANS OR SHOULD IT |
| | BE PER THE LONGEST LENGTH OF THE SYSTEM. THE INDICATED |
| | 7.1 TRAC PIPE TABLE IS NOT CLEAR ON HOW THIS TABLE |
| | WORKS, PLEASE CLARIFY. |
| | |
| | **NEW COMMENTS** |
| | |
| | 3. SHEET P4.16 PLEASE CORRELATE THE LONGEST RUN PER |
| | COMMENT #1. ** THE INDICATED LONGEST RUN OF 468'-0" IS |
| | WRONG PER THE INDICATED CORRESPONDING LENGTHS OF CUT |
| | SECTION OF PIPE IS 470'-7", HOWEVER UNTIL COMMENT #1 IS |
| | ADDRESSED AND THE PLANS ARE CORRELATED A GAS PLAN |
| | REVIEW CAN NOT BE COMPLETED. |
| | |
| | END OF COMMENTS: |
| | |