| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-09-16 00:00:00 | 1) EXIT SIGN NEEDED ON PAGE A0-6 NEAR | | | GARAGE DOOR ADJHACEENT TO ELEVATOR # 3. | | | | | | 2) SIGNAGE REQUIRED IN ALL STAIRWELLS | | | INDICATING THE STAIR NUMBER, THE | | | TERMINUS TOP AND BOTTOM AND THE FLOOR | | | LEVEL. | | | | | | 3) ALL CANVAS AWNINGS ARE TO BE FIRE | | | RETARDANT. | | | | | | 4) FIRE COMMAND ROOM REFERENCE STILL | | | PRESENT ON A6-O. | | | | | | 5) SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR FIRE PUMP AND APPURTENANT | | | EQUIPMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|