Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop M
Sequence Number 29
Notes
Date Text
2007-11-17 15:54:58M2.01 REVISION 18: DENIED.
 OUTSIDE AIR INTAKE FOR HP0.4 IS DIRECTLY ADJACENT TO A
 STREET OR ALLEY. MECHANICAL AND GRAVITY OUTSIDE AIR
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS IN ACCORDANCE WITH FBC,M 401.5.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: