2007-08-22 09:04:12REVISION M2.01 ADDED FSD
 ----------------DENIED-----------------
  
 PLAN SHOWS NEW TRANSFER DUCTOVER DOUBLE-DOORS WITH
 FSD. THE DEDIGNATION OF THE DAMPER IS FSD1.1 AND IT HAS
 THE NOTATION OF (N.C.). THIS IS THE COMMON ABBREVIATION
 FOR 'NORMALLY CLOSED' WHEN RELATED TO FIRE/SMOKE
 DAMPERS. THIS INFORMATION IS IN CONFLICT WITH THE
 FIRE/SMOKE DAMPER SCHEDULE ON M5.02, WHERE FSD1.1 IS
 SHOWN TO BE NORMALLY OPEN AND OPEN WHEN THERE IS NO
 POWER. PLEASE CLARIFY THE INTENT AND REQUIRED
 FUNCTIONALITY OF THIS DAMPER. COORDINATE WITH FSD
 SCHEDULE.
  