| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
25 |
|
| Notes |
| Date |
Text |
| 2007-08-22 09:04:12 | REVISION M2.01 ADDED FSD | | | ----------------DENIED----------------- | | | | | | PLAN SHOWS NEW TRANSFER DUCTOVER DOUBLE-DOORS WITH | | | FSD. THE DEDIGNATION OF THE DAMPER IS FSD1.1 AND IT HAS | | | THE NOTATION OF (N.C.). THIS IS THE COMMON ABBREVIATION | | | FOR 'NORMALLY CLOSED' WHEN RELATED TO FIRE/SMOKE | | | DAMPERS. THIS INFORMATION IS IN CONFLICT WITH THE | | | FIRE/SMOKE DAMPER SCHEDULE ON M5.02, WHERE FSD1.1 IS | | | SHOWN TO BE NORMALLY OPEN AND OPEN WHEN THERE IS NO | | | POWER. PLEASE CLARIFY THE INTENT AND REQUIRED | | | FUNCTIONALITY OF THIS DAMPER. COORDINATE WITH FSD | | | SCHEDULE. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|