| 2007-07-17 10:23:49 | REVISIONDENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | ******FROM PREVIOUS DENIED REVISION REVIEW |
| | |
| | 1. OK - DELETED |
| | |
| | 2. SHT P2.07 KEY NOTE #2 INDICATES A 6" SANITARY LINE |
| | FROM THE FLOOR ABOVE. THE FLOOR ABOVE AND THE FLOOR |
| | BELOW DO NOT INDICATE A 6" SANITARY LINE IN THIS |
| | LOCATION. PLEASE CLARIFY. SECTION 104.2.1. |
| | ****NOT ADDRESSED/NO RESPONSE |
| | |
| | 3. SHT P2.07 REVISION 3 BETWEEN COLUMNS 5 & 6 AND |
| | COLUMNS C & D DOES NOT INDICATE ANY CHANGE FROM |
| | PREVIOUS REVISION. PLEASE CLARIFY. |
| | ****NOT ADDRESSED/NO RESPONSE |
| | |
| | 4. OK |
| | |
| | 5. SHT P2.105 RWL DESIGNATIONS, (NUMBERS), HAVE BEEN |
| | REVISED TO BE 3" OR 4" STORM RISERS. PLEASE INDICATE |
| | WHY THE RWL DESIGNATIONS HAVE BEEN DELETED FROM THIS |
| | FLOOR. SECTION 104.2.1. |
| | ****NOT ADDRESSED/NO RESPONSE |
| | |
| | 6. SHT P4.14 RISER DIAGRAM SHOWS A TRENCH DRAIN |
| | CONNECTING TO A 4" EMERGENCY DRAIN, BUT ALSO TO A 4" |
| | DECK DRAIN. SEPARATE SYSTEMS ARE REQUIRED PER SECTION |
| | 1107.2.REVISION 5 FOR THIS AREA DOES NOT REFLECT THE |
| | FLOOR PLAN LAYOUT FOR THE DECK DRAIN & PLANTER DRAIN |
| | SHOWN ON SHT P2.07. THE SQUARE FOOTAGE AND DRAIN |
| | LAYOUTS ARE DIFFERENT ON THE FLOOR PLAN AND THE RISER |
| | DIAGRAM. PLEASE CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | ****RESPONSE NOTED, BUT THE BACKWATER VALVE AND SOME |
| | PIPING ARE STILL SHOWN ON THE RISER DIAGRAM. RISER DOES |
| | NOT REFLECT THE DECK PLAN. |
| | |