Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop P
Sequence Number 21
Notes
Date Text
2007-07-17 10:23:49REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 ******FROM PREVIOUS DENIED REVISION REVIEW
  
 1. OK - DELETED
  
 2. SHT P2.07 KEY NOTE #2 INDICATES A 6" SANITARY LINE
 FROM THE FLOOR ABOVE. THE FLOOR ABOVE AND THE FLOOR
 BELOW DO NOT INDICATE A 6" SANITARY LINE IN THIS
 LOCATION. PLEASE CLARIFY. SECTION 104.2.1.
 ****NOT ADDRESSED/NO RESPONSE
  
 3. SHT P2.07 REVISION 3 BETWEEN COLUMNS 5 & 6 AND
 COLUMNS C & D DOES NOT INDICATE ANY CHANGE FROM
 PREVIOUS REVISION. PLEASE CLARIFY.
 ****NOT ADDRESSED/NO RESPONSE
  
 4. OK
  
 5. SHT P2.105 RWL DESIGNATIONS, (NUMBERS), HAVE BEEN
 REVISED TO BE 3" OR 4" STORM RISERS. PLEASE INDICATE
 WHY THE RWL DESIGNATIONS HAVE BEEN DELETED FROM THIS
 FLOOR. SECTION 104.2.1.
 ****NOT ADDRESSED/NO RESPONSE
  
 6. SHT P4.14 RISER DIAGRAM SHOWS A TRENCH DRAIN
 CONNECTING TO A 4" EMERGENCY DRAIN, BUT ALSO TO A 4"
 DECK DRAIN. SEPARATE SYSTEMS ARE REQUIRED PER SECTION
 1107.2.REVISION 5 FOR THIS AREA DOES NOT REFLECT THE
 FLOOR PLAN LAYOUT FOR THE DECK DRAIN & PLANTER DRAIN
 SHOWN ON SHT P2.07. THE SQUARE FOOTAGE AND DRAIN
 LAYOUTS ARE DIFFERENT ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 ****RESPONSE NOTED, BUT THE BACKWATER VALVE AND SOME
 PIPING ARE STILL SHOWN ON THE RISER DIAGRAM. RISER DOES
 NOT REFLECT THE DECK PLAN.
  