| Date |
Text |
| 2004-07-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1) FROM PREVIOUS REVIEW: SHT A1.14 SEC- |
| | ONDARY DRAINS FOR ROOF DRAINS NOT SHOWN. |
| | SEE SECTIONS OF ROOF AT COLS. 5-7/B-C & |
| | 15-16/B-C1. NO SECONDARY DRAINS SHOWN |
| | FOR THESE UPPER ROOFS. SECTION 104.2.1. |
| | 2) FROM PREVIOUS REVIEW: SHTS A1.15, |
| | A1.16, & A1.17 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107. SHOW SF FOR EACH |
| | SECTION, ADDED 1/2 AREA FOR ALL VERTICAL |
| | WALLS INCLUDING PARAPETS, ALL SF FOR ALL |
| | ROOFS THAT DRAIN TO ROOF FROM ABOVE. - |
| | SHTS P2.17 & P2.18 SEE ROOF AREA ABOVE |
| | MECH/ELEVATOR/TOILET ROOMS ECT. NO INFOR |
| | MATION SHOWN FOR THE PRIMARY & SECONDARY |
| | ROOF DRAINS FOR THESE UPPER ROOFS. IF |
| | THESE ROOFS DRAIN TO SECTIONS OF THE |
| | ROOF BELOW THEN THOSE AREAS NEED TO RE- |
| | FLECT THE EXTRA SF. SHOW LOCATIONS OF |
| | THE ROOF DRAINS OF THE UPPER ROOFS. |
| | SECTION 104.2.1. |
| | 5) FROM PREVIOUS REVIEW: SHT A9.1 DE- |
| | TAILS A,C, & E SHOW FLUSH CONTROL PER |
| | 11-4.16.5. - ALSO NOTE THAT DETAIL "D" |
| | MENS TOILET AND DETAIL "F" MENS & WOMENS |
| | TOILETS FLUSH CONTROLS ARE ON THE WRONG |
| | SIDE. |
| | 8) FROM PREVIOUS REVIEW: SHTS A9.4 THRU |
| | A9.15 SHOW CLEAR FLOOR SPACE FOR WATER |
| | CLOSETS AS REQUIRED ON PAGE 7.43 OF THE |
| | FHA DESIGN MANUAL. |
| | 9) FROM PREVIOUS REVIEW: SHTS A9.4 THRU |
| | A9.15 WHERE APPLICABLE CORRECT THE FOLL- |
| | OWING ISSUES: |
| | B) INTERIOR ELEVATION SHALL REFLECT THE |
| | KEY PLAN WHEN SHOWING MEASUREMENTS FOR |
| | THE CENTERLINE OF THE TOILET OFF THE |
| | WALL OR ADJACENT FIXTURES/VANITY. SECT- |
| | ION 104.2.1. |
| | C) UNITS WITH SPECIFICATION "B" SHOW |
| | CLEAR FLOOR SPACE IN EACH BATHROOM. IN- |
| | DICATE WHICH BATHROOM WILL COMPLY AND |
| | SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED |
| | FIXTURES. FHA DESIGN MANUAL SEC. 104.2.1 |
| | D) THE 18" FROM THE CENTERLINE OF THE |
| | W/C TO THE WALL IS AN ABSOLUTE MEASURE- |
| | MENT. SEE PAGE 6.5 FHA DESIGN MANUAL. |
| | E) SOME UNITS DO NOT SHOW AN ELEVETION |
| | FOR THE WATER CLOSET. IF THE BATHROOM |
| | DESIGNATED TO COMPLY DOES NOT HAVE AN |
| | ELEVATION FOR THE W/C, PLEASE SUBMIT THE |
| | ELEVATION. SECTION 104.2.1. |
| | 12) NEW COMMENTS FROM RESPONSE: THE |
| | FOLLOWING SANITARY RISERS SHOWN ON THE |
| | SANITARY COLLECTION ISOMETRIC WERE NOT |
| | FOUND ON RISER SHEETS. S/124, S/125, |
| | S/126, S/127, S/128, S/129, & S/130. - |
| | THE FOLLOWING RISERS WERE NOT FOUND ON |
| | THE SANT. COLLECTION ISOMETRIC. S/48, & |
| | S/76. - S/75RISER SHOWS 10 DFU'S ON |
| | P4.03, BUT ON SHT P4.01 IT SHOWS 35 DFU |
| | - SANT. RISER "D", RISER S/70 SHOWS NO |
| | DFU'S ADD TO SYSTEM (100) - RISER "B", |
| | ARE THERE 2 S/29'S ? - RECALCULATE DFU'S |
| | ON RISER "G" - PLEASE CLARIFY AND CORRE- |
| | LATE PLANS. SECTION 104.2.1. |
| | 15) FROM PREVIOUS REVIEW: SHT P4.12, |
| | DETAIL #2 DOES NOT REFLECT THE FLOOR |
| | PLAN AT SECOND BATHROOM. (ROOM 119). |
| | DETAIL #4 DOES NOT REFLECT THE FLOOR |
| | PLAN AT SECOND BATHROOM. (ROOM 119). |
| | 16) FROM PREVIOUS REVIEW: SHT S P4.13 & |
| | P4.14 STORM COLLECTION ISOMETRIC, INDIC- |
| | ATE PIPE SIZE AND SHOW SF AS THEY ACCUM- |
| | ULATE IN THE SYSTEM. TABLES 1106.2 AND |
| | 1106.3. CHECK SIZINT AT "K" RISER. DOES |
| | NOT CORRELATE. |
| | 19) FROM PREVIOUS REVIEW: TRASH CHUTE |
| | WASH DOWN LINES ARE NOT SHOWN. SECTION |
| | 104.2.1. |
| | 20) FROM PREVIOUS REVIEW: SWIMMING POOL |
| | LINE NOT SHOWN. SECTION 104.2.1. |
| | 21) FROM PREVIOUS REVIEW: THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR APPLICATION |
| | FOR SEPARATE GAS PERMIT. |
| | F) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA-54, NFPA-58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC. 402.2 |
| | ***NEW COMMENT - MANUF. SHEETS REQUIRED |
| | FOR PRESSURE REGULATORS FROM 2LB SYSTEM |
| | TO LOW PRESSURE REQUIRED AT EACH GAS |
| | FIXTURE. SECTION 410. |
| | 24) FROM PREVIOUS REVIEW: SHOW APPORVAL |
| | FOR SOVENT SYSTEM BY AN APPROVED TESTING |
| | AGENCY. SHOW TESTING FOR FLOW RATES. |
| | SECTION 104.2.1. |
| | 25) FROM PREVIOUS REVIEW: MANY SANITARY |
| | RISERS DO NOT COMPLY WITH REQUIREMENTS |
| | INDICATED ON SHT. P5.02. SECTION 104.2.1 |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |