Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW: SHT A1.14 SEC-
 ONDARY DRAINS FOR ROOF DRAINS NOT SHOWN.
 SEE SECTIONS OF ROOF AT COLS. 5-7/B-C &
 15-16/B-C1. NO SECONDARY DRAINS SHOWN
 FOR THESE UPPER ROOFS. SECTION 104.2.1.
 2) FROM PREVIOUS REVIEW: SHTS A1.15,
 A1.16, & A1.17 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. SHOW SF FOR EACH
 SECTION, ADDED 1/2 AREA FOR ALL VERTICAL
 WALLS INCLUDING PARAPETS, ALL SF FOR ALL
 ROOFS THAT DRAIN TO ROOF FROM ABOVE. -
 SHTS P2.17 & P2.18 SEE ROOF AREA ABOVE
 MECH/ELEVATOR/TOILET ROOMS ECT. NO INFOR
 MATION SHOWN FOR THE PRIMARY & SECONDARY
 ROOF DRAINS FOR THESE UPPER ROOFS. IF
 THESE ROOFS DRAIN TO SECTIONS OF THE
 ROOF BELOW THEN THOSE AREAS NEED TO RE-
 FLECT THE EXTRA SF. SHOW LOCATIONS OF
 THE ROOF DRAINS OF THE UPPER ROOFS.
 SECTION 104.2.1.
 5) FROM PREVIOUS REVIEW: SHT A9.1 DE-
 TAILS A,C, & E SHOW FLUSH CONTROL PER
 11-4.16.5. - ALSO NOTE THAT DETAIL "D"
 MENS TOILET AND DETAIL "F" MENS & WOMENS
 TOILETS FLUSH CONTROLS ARE ON THE WRONG
 SIDE.
 8) FROM PREVIOUS REVIEW: SHTS A9.4 THRU
 A9.15 SHOW CLEAR FLOOR SPACE FOR WATER
 CLOSETS AS REQUIRED ON PAGE 7.43 OF THE
 FHA DESIGN MANUAL.
 9) FROM PREVIOUS REVIEW: SHTS A9.4 THRU
 A9.15 WHERE APPLICABLE CORRECT THE FOLL-
 OWING ISSUES:
 B) INTERIOR ELEVATION SHALL REFLECT THE
 KEY PLAN WHEN SHOWING MEASUREMENTS FOR
 THE CENTERLINE OF THE TOILET OFF THE
 WALL OR ADJACENT FIXTURES/VANITY. SECT-
 ION 104.2.1.
 C) UNITS WITH SPECIFICATION "B" SHOW
 CLEAR FLOOR SPACE IN EACH BATHROOM. IN-
 DICATE WHICH BATHROOM WILL COMPLY AND
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES. FHA DESIGN MANUAL SEC. 104.2.1
 D) THE 18" FROM THE CENTERLINE OF THE
 W/C TO THE WALL IS AN ABSOLUTE MEASURE-
 MENT. SEE PAGE 6.5 FHA DESIGN MANUAL.
 E) SOME UNITS DO NOT SHOW AN ELEVETION
 FOR THE WATER CLOSET. IF THE BATHROOM
 DESIGNATED TO COMPLY DOES NOT HAVE AN
 ELEVATION FOR THE W/C, PLEASE SUBMIT THE
 ELEVATION. SECTION 104.2.1.
 12) NEW COMMENTS FROM RESPONSE: THE
 FOLLOWING SANITARY RISERS SHOWN ON THE
 SANITARY COLLECTION ISOMETRIC WERE NOT
 FOUND ON RISER SHEETS. S/124, S/125,
 S/126, S/127, S/128, S/129, & S/130. -
 THE FOLLOWING RISERS WERE NOT FOUND ON
 THE SANT. COLLECTION ISOMETRIC. S/48, &
 S/76. - S/75RISER SHOWS 10 DFU'S ON
 P4.03, BUT ON SHT P4.01 IT SHOWS 35 DFU
 - SANT. RISER "D", RISER S/70 SHOWS NO
 DFU'S ADD TO SYSTEM (100) - RISER "B",
 ARE THERE 2 S/29'S ? - RECALCULATE DFU'S
 ON RISER "G" - PLEASE CLARIFY AND CORRE-
 LATE PLANS. SECTION 104.2.1.
 15) FROM PREVIOUS REVIEW: SHT P4.12,
 DETAIL #2 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM. (ROOM 119).
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM. (ROOM 119).
 16) FROM PREVIOUS REVIEW: SHT S P4.13 &
 P4.14 STORM COLLECTION ISOMETRIC, INDIC-
 ATE PIPE SIZE AND SHOW SF AS THEY ACCUM-
 ULATE IN THE SYSTEM. TABLES 1106.2 AND
 1106.3. CHECK SIZINT AT "K" RISER. DOES
 NOT CORRELATE.
 19) FROM PREVIOUS REVIEW: TRASH CHUTE
 WASH DOWN LINES ARE NOT SHOWN. SECTION
 104.2.1.
 20) FROM PREVIOUS REVIEW: SWIMMING POOL
 LINE NOT SHOWN. SECTION 104.2.1.
 21) FROM PREVIOUS REVIEW: THE FOLLOWING
 INFORMATION IS REQUIRED FOR APPLICATION
 FOR SEPARATE GAS PERMIT.
 F) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA-54, NFPA-58, AND THE
 FBC-2001 FUEL GAS CODE SEC. 402.2
 ***NEW COMMENT - MANUF. SHEETS REQUIRED
 FOR PRESSURE REGULATORS FROM 2LB SYSTEM
 TO LOW PRESSURE REQUIRED AT EACH GAS
 FIXTURE. SECTION 410.
 24) FROM PREVIOUS REVIEW: SHOW APPORVAL
 FOR SOVENT SYSTEM BY AN APPROVED TESTING
 AGENCY. SHOW TESTING FOR FLOW RATES.
 SECTION 104.2.1.
 25) FROM PREVIOUS REVIEW: MANY SANITARY
 RISERS DO NOT COMPLY WITH REQUIREMENTS
 INDICATED ON SHT. P5.02. SECTION 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved