Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop M
Sequence Number 2
Notes
Date Text
2004-07-13 00:00:00DENIED:
 SUBMITTAL BOOK DOES NOT HAVE A SUBMITTAL
 FOR THE GENERATOR OR THE BOILER.
  
 1.PLAN SHEET M2.01 GENERATOR,
 DEMENSIONS GIVEN FROM THE MIDDLE OF THE
 ALLEY IS 10" (INCHES) SHOULD READ 10'
 (FEET).
  
 2.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE GENERATOR.PLEASE NOTE PLAN
 SHEET M2.01 INDICATES A FIRE DAMPER AT
 THE RADIATOR EXHAUST.IS THIS ALLOWED
 BY THE MANUFACTURER?
  
 3.M2.01MUFFLER EXHAUST PIPE, PROVIDE
 INFORMATION FROM THE MANUFACTURER THAT
 THE LENGTH OF THE EXHAUST WILL NOT HAVE
 AN ADVERSE EFFECT ON THE GENERATOR.
  
 4.PROVIDE ELEVATION (BOP) OF THE
 MUFFLER PIPE.
  
 5.M2.01 30" X 10" INTAKE DUCT INTO THE
 A/C CLOSET & EXERCISE ROOM, DUCT
 PENETRATES A RATED WALL THEREFORE A
 FIRE DAMPER IS REQUIRED.
  
 6.M2.02 CONDENSING UNITS INSTALLED
 TIGHT TO DECK.PLEASE PROVIDE
 ELEVATION.
  
 7.REFERENCE COMMENT #10 ON THE
 PREVIOUS REVIEW;DRYER SHOULD BE
 INCAPACITATED SHOULD THE BOOSTER FAN
 FAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.