| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-13 00:00:00 | DENIED: | | | SUBMITTAL BOOK DOES NOT HAVE A SUBMITTAL | | | FOR THE GENERATOR OR THE BOILER. | | | | | | 1.PLAN SHEET M2.01 GENERATOR, | | | DEMENSIONS GIVEN FROM THE MIDDLE OF THE | | | ALLEY IS 10" (INCHES) SHOULD READ 10' | | | (FEET). | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE GENERATOR.PLEASE NOTE PLAN | | | SHEET M2.01 INDICATES A FIRE DAMPER AT | | | THE RADIATOR EXHAUST.IS THIS ALLOWED | | | BY THE MANUFACTURER? | | | | | | 3.M2.01MUFFLER EXHAUST PIPE, PROVIDE | | | INFORMATION FROM THE MANUFACTURER THAT | | | THE LENGTH OF THE EXHAUST WILL NOT HAVE | | | AN ADVERSE EFFECT ON THE GENERATOR. | | | | | | 4.PROVIDE ELEVATION (BOP) OF THE | | | MUFFLER PIPE. | | | | | | 5.M2.01 30" X 10" INTAKE DUCT INTO THE | | | A/C CLOSET & EXERCISE ROOM, DUCT | | | PENETRATES A RATED WALL THEREFORE A | | | FIRE DAMPER IS REQUIRED. | | | | | | 6.M2.02 CONDENSING UNITS INSTALLED | | | TIGHT TO DECK.PLEASE PROVIDE | | | ELEVATION. | | | | | | 7.REFERENCE COMMENT #10 ON THE | | | PREVIOUS REVIEW;DRYER SHOULD BE | | | INCAPACITATED SHOULD THE BOOSTER FAN | | | FAIL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|