Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop G
Sequence Number 2
Notes
Date Text
2007-12-04 17:36:47DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P4.16 SHOW THE LENGTHS OF PIPE FROM THE METER TO
 THE FIRST 8'0" RISER AND SHOW THE LEGHTS OF PIPE FROM
 THE 200'0" TO THE REGULATOR DOWNSTREAM OF ITEM (A). SO
 THE TOTAL DEVELOPED LENGHT CAN BE VERIFIED.
  
 2. SHT P4.1.6 SUBMIT THE COMPUTATIONS FOR THE EQUATION
 USED TO SIZE THE PIPE PER SECTION 402.3 (2) SO THAT ALL
 FIGURES AND OUTCOME CAN BE VERIFIED BY AN INDEPENDANT
 ENGINEER.
  
 3. SUBMIT THE CALCULATIONS TO AN INDEPENDENT ENGINEER
 FOR VERIFICATION AND THEN RESUBMIT THE GAS REVISION
 WITH THE INDEPENDENT ENGINEERS FINDINGSFOR REVIEW.
  
 4. SHT P4.1.6 INDICATE THE MATERIAL FOR EACH SECTION OF
 PIPE AS SOME OF THE PIPING WAS CHANGED FROM BLACK IRON
 PIPE TO CSST PIPE.
  