Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-07-30 00:00:001) MISSING EXIT SIGNS ON AO-5 FOR
 THE RESIDENTIAL ELEMENT.
  
 2) EXIT SIGNS SHALL NOT EXCEED 100
 FEET.
  
 3) SIGNS REQUIRED ON EXIT DOORS THAT
 FACE THE ALLEY. "EXIT DOOR, DO NOT
 BLOCK".
  
 4) THE WALLS SEPARATING THE GARAGE FROM
 OTHER PORTIONS OF THE BUILDING SHALL
 BE AT LEAST TWO HOUR RATED WITH HOUR AND
 A HALF OPENING PROTECTIVES.
  
 5) A FIRE COMMAND ROOM NOTE APPEARS ON
 PAGE A1-2. THIS APPEARS TO BE A
 DIFFERENT LOCATION THAN PREVIOUSLY
 PLAN SHEETS.
  
 6) EXTERIOR PLYWOOD DECKING DESCRIBED
 ON PAGE A1-16. THE BUILDING AGAIN
 IS LOCATED IN THE CITY FIRE LIMITS
 CERTAIN RESTRICTIONS WILL APPLY.
 ALSO SAME NOTES APPEAR ON PAGE A1-17.
  
 7) A FIRE COMMAND ROOM NOTE APPEARS
 ON PAGE A2-1. PLEASE CLARIFY.
  
 8) ELECTRONIC SWITCHES, CHAIN AND
 LOCK WILL BE REQUIRED ON FIRE LINE
 BACKFLOW DEVICE. NOTED ON PAGE FP2.01
  
 9) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON PAGE FP2.01 IS IN A DIFFERENT
 LOCATION AS ILLUSTRATED ON PREVIOUS
 PAGES.
  
 10) SAME CONDITION EXISTS ON PAGE
 FP2.02.
  
 11) MECHANICAL AREA ON PAGE FP2.02
 NOT FIRE SPRINKLER PROTECTED.
  
 12) PUMP ROOM 090 IS NOT FIRE
 SPRINKLER PROTECTED. WHY?
  
 13) WHY IS POOL EQUIPMENT ROOM 091
 NOT FIRE SPRINKLER PROTECTED. WHY?
  
 14) PLEASE EXPLAIN THE 1000 GPM FIRE
 PUMP. HOW MANY REQUIRED STANDPIPES
 ARE NEEDED TO MAKE THE BUILDING
 WORK.
  
 15) A NEW WATER FLOW TEST WILL
 BE REQUIRED FOR THE PROJECT. THE DATA
 SHOWN ON PAGE FP4.01 DISPLAY A DATE
 OF 8.8.03 WHICH MAKES THIS TEST
 MORE THAN ONE YEAR OLD. PLEASE
 SCHEDULE.
  
 16) PRESSURE REGULATING DEVICES SHOWN
 ON PAGE FP4.01. WILL THESE BE SET
 IN THE FIELD OR FACTORY SET.
  
 17) PLEASE DOCUMENT ON THE PLANS
 WHEN THE BATHROOMS WILL BE FIRE
 SPRINKLERED AND WHEN THEY ARE NOT.
  
 18) PLEASE EXPLAIN SMOKE DETECTORS
 LOCATED DIRECTLY OUTSIDE OF STAIRWAYS
 ON PAGE FA2.04.
  
 19) WHAT IS THE VOICE EVACUATION
 MESSAGE EXPECTED TO SAY AFTER THE
 FIRE ALARM SYSTEM IS INITIATED.
  
 20) THE FIRE ALARM SEQUENCE OF
 OPERATION FOR FIRE ALARM ITEM # 3
 IS INCORRECT. SMOKE DETECTORS WHEN
 ACTIVATED SHALL ALSO CAUSE THE
 BUILDING TO GO INTO FIRE ALARM
 MODE.
  
 21) HOW WILL THE CARBON MONOXIDE
 DETECTORS BE TESTED. PLEASE PROVIDE
 A TESTING CRITERIA. CALIBRATION GAS
 WILL BE REQUIRED TO SET THE POINTS
 ON THE DETECTOR.
  
 22) ALL EXTERIOR STAIRS ARE TO
 BE SLIP RESISTANT.
  
 23) NO FIRE HOSE VALVE CONNECTIONS
 SHOWN ON LIFE SAFETY ROOF PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910