| Date |
Text |
| 2004-07-30 00:00:00 | 1) MISSING EXIT SIGNS ON AO-5 FOR |
| | THE RESIDENTIAL ELEMENT. |
| | |
| | 2) EXIT SIGNS SHALL NOT EXCEED 100 |
| | FEET. |
| | |
| | 3) SIGNS REQUIRED ON EXIT DOORS THAT |
| | FACE THE ALLEY. "EXIT DOOR, DO NOT |
| | BLOCK". |
| | |
| | 4) THE WALLS SEPARATING THE GARAGE FROM |
| | OTHER PORTIONS OF THE BUILDING SHALL |
| | BE AT LEAST TWO HOUR RATED WITH HOUR AND |
| | A HALF OPENING PROTECTIVES. |
| | |
| | 5) A FIRE COMMAND ROOM NOTE APPEARS ON |
| | PAGE A1-2. THIS APPEARS TO BE A |
| | DIFFERENT LOCATION THAN PREVIOUSLY |
| | PLAN SHEETS. |
| | |
| | 6) EXTERIOR PLYWOOD DECKING DESCRIBED |
| | ON PAGE A1-16. THE BUILDING AGAIN |
| | IS LOCATED IN THE CITY FIRE LIMITS |
| | CERTAIN RESTRICTIONS WILL APPLY. |
| | ALSO SAME NOTES APPEAR ON PAGE A1-17. |
| | |
| | 7) A FIRE COMMAND ROOM NOTE APPEARS |
| | ON PAGE A2-1. PLEASE CLARIFY. |
| | |
| | 8) ELECTRONIC SWITCHES, CHAIN AND |
| | LOCK WILL BE REQUIRED ON FIRE LINE |
| | BACKFLOW DEVICE. NOTED ON PAGE FP2.01 |
| | |
| | 9) THE FIRE DEPARTMENT CONNECTION SHOWN |
| | ON PAGE FP2.01 IS IN A DIFFERENT |
| | LOCATION AS ILLUSTRATED ON PREVIOUS |
| | PAGES. |
| | |
| | 10) SAME CONDITION EXISTS ON PAGE |
| | FP2.02. |
| | |
| | 11) MECHANICAL AREA ON PAGE FP2.02 |
| | NOT FIRE SPRINKLER PROTECTED. |
| | |
| | 12) PUMP ROOM 090 IS NOT FIRE |
| | SPRINKLER PROTECTED. WHY? |
| | |
| | 13) WHY IS POOL EQUIPMENT ROOM 091 |
| | NOT FIRE SPRINKLER PROTECTED. WHY? |
| | |
| | 14) PLEASE EXPLAIN THE 1000 GPM FIRE |
| | PUMP. HOW MANY REQUIRED STANDPIPES |
| | ARE NEEDED TO MAKE THE BUILDING |
| | WORK. |
| | |
| | 15) A NEW WATER FLOW TEST WILL |
| | BE REQUIRED FOR THE PROJECT. THE DATA |
| | SHOWN ON PAGE FP4.01 DISPLAY A DATE |
| | OF 8.8.03 WHICH MAKES THIS TEST |
| | MORE THAN ONE YEAR OLD. PLEASE |
| | SCHEDULE. |
| | |
| | 16) PRESSURE REGULATING DEVICES SHOWN |
| | ON PAGE FP4.01. WILL THESE BE SET |
| | IN THE FIELD OR FACTORY SET. |
| | |
| | 17) PLEASE DOCUMENT ON THE PLANS |
| | WHEN THE BATHROOMS WILL BE FIRE |
| | SPRINKLERED AND WHEN THEY ARE NOT. |
| | |
| | 18) PLEASE EXPLAIN SMOKE DETECTORS |
| | LOCATED DIRECTLY OUTSIDE OF STAIRWAYS |
| | ON PAGE FA2.04. |
| | |
| | 19) WHAT IS THE VOICE EVACUATION |
| | MESSAGE EXPECTED TO SAY AFTER THE |
| | FIRE ALARM SYSTEM IS INITIATED. |
| | |
| | 20) THE FIRE ALARM SEQUENCE OF |
| | OPERATION FOR FIRE ALARM ITEM # 3 |
| | IS INCORRECT. SMOKE DETECTORS WHEN |
| | ACTIVATED SHALL ALSO CAUSE THE |
| | BUILDING TO GO INTO FIRE ALARM |
| | MODE. |
| | |
| | 21) HOW WILL THE CARBON MONOXIDE |
| | DETECTORS BE TESTED. PLEASE PROVIDE |
| | A TESTING CRITERIA. CALIBRATION GAS |
| | WILL BE REQUIRED TO SET THE POINTS |
| | ON THE DETECTOR. |
| | |
| | 22) ALL EXTERIOR STAIRS ARE TO |
| | BE SLIP RESISTANT. |
| | |
| | 23) NO FIRE HOSE VALVE CONNECTIONS |
| | SHOWN ON LIFE SAFETY ROOF PLAN. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |