Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-26 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE THERE IS SOME CIRCUIT
 -ING STILL MISSING IN APT UNITS.
 PLEASE SEE SOME GFI'S IN BATHS/CLOSET
 RECEPTS/ SD'S ETC MAY BE MISSING #'S.
 3.01,5.02,3.02 ETC
  
 2)NOTE: PLEASE SEE ELECTRICAL NOTES ON
 6.01 MENTIONS SD'S TO BE WIRED AHEAD
 OF BRANCH CIRCUIT FOR LIGHTING WITH ARC-
 FAULT PROTECTION; HOWEVER UNIT LAYOUTS
 INDICATE SD'S ON MANY OF THE RECEPT
 CIRCUITS.? PLEASE CORRELATE
  
 3)NOTE: PLEASE SEE 2002 NEC 210.12B FOR
 REQUIRED ARC FAULT PROETCTIONS.
 PANEL NOTES MENTIONS PROTECTION FOR
 BRANCH CIRCUITS AS NOTED TYP,NOTE#5, YET
 PLEASE SEE J-BOXES SHOWN IN MOST BEDRMS
 ARE NOT ON CIRCUITS AS NOTED. THEY ARE
 ON A SEPARATE LT BRANCH CIRCUIT W/OUT
 ARC FAULT PROTECTION.
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE SOME UNITS ARE MISSING SD'S
 ON FIRST FLR AREA LEADING TO FLR ABOVE,
 PLEASE ALSO SEE PH UNITS.
 8-1.4.1.6.2NFPA-72
  
 5)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. 3.03 A-4, 3.10 PH-9 AND OTHER
 UNITS CONTAINING 2'OF WALL SPACE INCLUD-
 -ING KITCHEN WALLS.
  
 6)NOTE: PLEASE SEE NOTES ON PH PLANS,
 (3.07,3.08) ETC REFERENCE TO SEE LIGHT-
 -ING LAYOUTS ON 2.15&2.16.
 PLEASE SEE 2.15,2.16 DO NOT SEEM TO
 CONTAIN ANY LAYOUT OF THESE LTS REFER-
 -ENCED.
  
 7)NOTE: PLEASE SEE ROOM DESIGNATIONS ARE
 PROVIDED ON SOME UNITS AND NOT OTHERS?
 PLEASE PROVIDE.
  
 8)NOTE: PLEASE SEE "ELECTRICAL NOTE"
 ON 6.01 STILL REFERENCE MIN AWG TO BE
 #12, YET PANELS SCHEDULES STILL INDICATE
 #14? PLEASE CORRELATE.
  
 9)NOTE: PLEASE ALSO SEE NOTE#1 ON
 ELECTRICAL NOTES, MENTIONS ALUM #3 AND
 LARGER PERMITTEED TO BE USED. PLEASE
 SEE LOCAL AMENDMENTS, 310.2-1 ALUM ONLY
 PERMITTED FOR #2 AND LARGER.
 PLEASE ALSO NOTE: ALUM CONDUCTORS ARE
 NOT PERMITTED FOR GROUNDING OR BONDING
 PER 310.2.2,250.62
  
 10)NOTE: PLEASE SEE RISER DIAGRAM ON
 SHEET 4.01, PLEASE SEE "DRAWING KEYNOTES
 ,BUSDUCT ON RISER NOTES #1 AND #3.
 PLEASE SEE NOTE # 3 MENTIONS BUS DUCT,
 YET NOTE#1 REFERENCES SUPPORT FOR CABLES
 ? PLEASE CORRELATE.
  
 11)NOTE: PLEASE SEE METER SUMMARY, MC-1
 SHOWS 3P-600A OCP, YET MC-1 ON LOAD
 SUMMARY MENTIONS A 1000A MCB IN A 1200A
 MAIN.
 PLEASE CORRELATE OVER CURRENT PROTECTION
  
  
 12)NOTE: PLEASE SEE RISER INDICATES
 ON FEEDER SCHEDULE (F-3) CONDUIT AND
 CONDUCTORS FROM FPL TO MC-1.
 PLEASE SEE ELECTRICAL ROOM LAYOUT ON
 3.12 APPEARS TO HAVE MORE THAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE BLDG ELEC-
 -TRICAL RM. 230.70,230.6
 THESE MUST BE ENCASED ON A MIN OF 2"
 OF CONCRETE.
 PLEASE PROVIDE A NOTE ON RISER/PLANS
 WHICH REFERENCES TO THESE FEEDERS TO
 BE "ENCASED IN CONCRETE"
  
 13)NOTE:PLEASE SEE RISER DIAGRAM SHOWS
 POWER COMING IN FROM FPL INTO FIRE PUMP
 MAIN, YET RISER ALSO SHOWS POWER COMING
 FROM GENERATOR INTO SAME FIRE PUMP MAIN.
 PLEASE SEE THESE FEEDS WOULD NEED TO
 ENTER INTO ATS SWITCH AND THEN TO MAIN.
 IF GENERATOR IS RUNNING DUE TO A POWER
 FAILURE AND THE POWER RETURNS FROM FPL,
 THERE IS A POTENTIAL OF POWER COMING
 FROM TWO DIFFERENT SOURCES AS SHOWN.
 THIS WOULD CREATE AN FIRE/LIFE SAFETY
 HAZARD.
  
 14)NOTE: PLEASE SEE SOME CLOTHES CLOSETS
 ARE SHOWING RECEPTS. IF THESE ARE FOR
 ANY TYPE OF "PLUG-IN" LV TRANSFORMERS
 FOR ALARM PANELS ETC. THESE WILL NOT
 BE PERMITTED DUE TO THE CLOSE PROXIMITY
 OF EASILY IGNITIBLE MATERIALS. 240.24D
 PLEASE SEE SOME UNIT SHOW IN ALUNDRY RMS
 WHICH ARE OK.
 NOTE: IF RECEPTS ARE MOVED TO AN ARE OF
 CLOSET WHERE ITEMS ARE NOT ABLE TO BE
 STORED NEXT TO UNIT THEN PLEASE REVISE
 LOCATION. (ABOVE DRS)?
  
 15)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS IN REFERENCE TO SPECS SHEETS
 NOT SUBMITTED FOR FIRE PUMP/GEN AND ASSC
 EQUIPMENT INCLUDING FUEL TANKS.
 PLEASE KNOW THAT SINCE NO SPECS SHEETS
 WERE SUBMITTED FOR FIRE PUMP, GENERATOR,
 ATS, FUEL TANKS ETC WILL ALL BE REQUIRED
 TO BE UNDER SEPARATE PERMITS. ELEC/FIRE/
 MECH ETC.
 THESE WILL ALSO BE REQUIRED TO PAY
 SEPARATE PERMIT FEES FOR EACH BASED ON
 THE VALUE OF EQUIPMENT AND LABOR.
 FBC 104.6.5
  
 16)NOTE: PLEASE SEE SOME ARCH SHEETS
 HAVE COME BACK IN WITHOUT AN ORIGINAL
 SIGNATURE. THERE ARE NUMEROUS SHEETS
 WITH A "RUBBER STAMP" SIGNATURE.
 FS 481.221 FAC 61G1-16 REQUIRES AN
 ORIGINAL SIGNATURE. THIS COMMENT IS FOR
 ARCH SHEETS AND NOT E-SHEETS BY
 STEVEN FELLER INC.
  
 PLEASE SEE THAT ONE SET REVIEWED HAS
 MANY OF THE ABOVE COMMENTS REDLINED AND/
 OR CIRCLED FOR LOCATIONS AND ITEMS
 MENTIONED IN COMMENTS.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 ABOUT ANY OF THE ABOVE COMMENTS, PLEASE
 DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]