| Date |
Text |
| 2004-07-26 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE THERE IS SOME CIRCUIT |
| | -ING STILL MISSING IN APT UNITS. |
| | PLEASE SEE SOME GFI'S IN BATHS/CLOSET |
| | RECEPTS/ SD'S ETC MAY BE MISSING #'S. |
| | 3.01,5.02,3.02 ETC |
| | |
| | 2)NOTE: PLEASE SEE ELECTRICAL NOTES ON |
| | 6.01 MENTIONS SD'S TO BE WIRED AHEAD |
| | OF BRANCH CIRCUIT FOR LIGHTING WITH ARC- |
| | FAULT PROTECTION; HOWEVER UNIT LAYOUTS |
| | INDICATE SD'S ON MANY OF THE RECEPT |
| | CIRCUITS.? PLEASE CORRELATE |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC 210.12B FOR |
| | REQUIRED ARC FAULT PROETCTIONS. |
| | PANEL NOTES MENTIONS PROTECTION FOR |
| | BRANCH CIRCUITS AS NOTED TYP,NOTE#5, YET |
| | PLEASE SEE J-BOXES SHOWN IN MOST BEDRMS |
| | ARE NOT ON CIRCUITS AS NOTED. THEY ARE |
| | ON A SEPARATE LT BRANCH CIRCUIT W/OUT |
| | ARC FAULT PROTECTION. |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE SOME UNITS ARE MISSING SD'S |
| | ON FIRST FLR AREA LEADING TO FLR ABOVE, |
| | PLEASE ALSO SEE PH UNITS. |
| | 8-1.4.1.6.2NFPA-72 |
| | |
| | 5)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. 3.03 A-4, 3.10 PH-9 AND OTHER |
| | UNITS CONTAINING 2'OF WALL SPACE INCLUD- |
| | -ING KITCHEN WALLS. |
| | |
| | 6)NOTE: PLEASE SEE NOTES ON PH PLANS, |
| | (3.07,3.08) ETC REFERENCE TO SEE LIGHT- |
| | -ING LAYOUTS ON 2.15&2.16. |
| | PLEASE SEE 2.15,2.16 DO NOT SEEM TO |
| | CONTAIN ANY LAYOUT OF THESE LTS REFER- |
| | -ENCED. |
| | |
| | 7)NOTE: PLEASE SEE ROOM DESIGNATIONS ARE |
| | PROVIDED ON SOME UNITS AND NOT OTHERS? |
| | PLEASE PROVIDE. |
| | |
| | 8)NOTE: PLEASE SEE "ELECTRICAL NOTE" |
| | ON 6.01 STILL REFERENCE MIN AWG TO BE |
| | #12, YET PANELS SCHEDULES STILL INDICATE |
| | #14? PLEASE CORRELATE. |
| | |
| | 9)NOTE: PLEASE ALSO SEE NOTE#1 ON |
| | ELECTRICAL NOTES, MENTIONS ALUM #3 AND |
| | LARGER PERMITTEED TO BE USED. PLEASE |
| | SEE LOCAL AMENDMENTS, 310.2-1 ALUM ONLY |
| | PERMITTED FOR #2 AND LARGER. |
| | PLEASE ALSO NOTE: ALUM CONDUCTORS ARE |
| | NOT PERMITTED FOR GROUNDING OR BONDING |
| | PER 310.2.2,250.62 |
| | |
| | 10)NOTE: PLEASE SEE RISER DIAGRAM ON |
| | SHEET 4.01, PLEASE SEE "DRAWING KEYNOTES |
| | ,BUSDUCT ON RISER NOTES #1 AND #3. |
| | PLEASE SEE NOTE # 3 MENTIONS BUS DUCT, |
| | YET NOTE#1 REFERENCES SUPPORT FOR CABLES |
| | ? PLEASE CORRELATE. |
| | |
| | 11)NOTE: PLEASE SEE METER SUMMARY, MC-1 |
| | SHOWS 3P-600A OCP, YET MC-1 ON LOAD |
| | SUMMARY MENTIONS A 1000A MCB IN A 1200A |
| | MAIN. |
| | PLEASE CORRELATE OVER CURRENT PROTECTION |
| | |
| | |
| | 12)NOTE: PLEASE SEE RISER INDICATES |
| | ON FEEDER SCHEDULE (F-3) CONDUIT AND |
| | CONDUCTORS FROM FPL TO MC-1. |
| | PLEASE SEE ELECTRICAL ROOM LAYOUT ON |
| | 3.12 APPEARS TO HAVE MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS INSIDE BLDG ELEC- |
| | -TRICAL RM. 230.70,230.6 |
| | THESE MUST BE ENCASED ON A MIN OF 2" |
| | OF CONCRETE. |
| | PLEASE PROVIDE A NOTE ON RISER/PLANS |
| | WHICH REFERENCES TO THESE FEEDERS TO |
| | BE "ENCASED IN CONCRETE" |
| | |
| | 13)NOTE:PLEASE SEE RISER DIAGRAM SHOWS |
| | POWER COMING IN FROM FPL INTO FIRE PUMP |
| | MAIN, YET RISER ALSO SHOWS POWER COMING |
| | FROM GENERATOR INTO SAME FIRE PUMP MAIN. |
| | PLEASE SEE THESE FEEDS WOULD NEED TO |
| | ENTER INTO ATS SWITCH AND THEN TO MAIN. |
| | IF GENERATOR IS RUNNING DUE TO A POWER |
| | FAILURE AND THE POWER RETURNS FROM FPL, |
| | THERE IS A POTENTIAL OF POWER COMING |
| | FROM TWO DIFFERENT SOURCES AS SHOWN. |
| | THIS WOULD CREATE AN FIRE/LIFE SAFETY |
| | HAZARD. |
| | |
| | 14)NOTE: PLEASE SEE SOME CLOTHES CLOSETS |
| | ARE SHOWING RECEPTS. IF THESE ARE FOR |
| | ANY TYPE OF "PLUG-IN" LV TRANSFORMERS |
| | FOR ALARM PANELS ETC. THESE WILL NOT |
| | BE PERMITTED DUE TO THE CLOSE PROXIMITY |
| | OF EASILY IGNITIBLE MATERIALS. 240.24D |
| | PLEASE SEE SOME UNIT SHOW IN ALUNDRY RMS |
| | WHICH ARE OK. |
| | NOTE: IF RECEPTS ARE MOVED TO AN ARE OF |
| | CLOSET WHERE ITEMS ARE NOT ABLE TO BE |
| | STORED NEXT TO UNIT THEN PLEASE REVISE |
| | LOCATION. (ABOVE DRS)? |
| | |
| | 15)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW |
| | COMMENTS IN REFERENCE TO SPECS SHEETS |
| | NOT SUBMITTED FOR FIRE PUMP/GEN AND ASSC |
| | EQUIPMENT INCLUDING FUEL TANKS. |
| | PLEASE KNOW THAT SINCE NO SPECS SHEETS |
| | WERE SUBMITTED FOR FIRE PUMP, GENERATOR, |
| | ATS, FUEL TANKS ETC WILL ALL BE REQUIRED |
| | TO BE UNDER SEPARATE PERMITS. ELEC/FIRE/ |
| | MECH ETC. |
| | THESE WILL ALSO BE REQUIRED TO PAY |
| | SEPARATE PERMIT FEES FOR EACH BASED ON |
| | THE VALUE OF EQUIPMENT AND LABOR. |
| | FBC 104.6.5 |
| | |
| | 16)NOTE: PLEASE SEE SOME ARCH SHEETS |
| | HAVE COME BACK IN WITHOUT AN ORIGINAL |
| | SIGNATURE. THERE ARE NUMEROUS SHEETS |
| | WITH A "RUBBER STAMP" SIGNATURE. |
| | FS 481.221 FAC 61G1-16 REQUIRES AN |
| | ORIGINAL SIGNATURE. THIS COMMENT IS FOR |
| | ARCH SHEETS AND NOT E-SHEETS BY |
| | STEVEN FELLER INC. |
| | |
| | PLEASE SEE THAT ONE SET REVIEWED HAS |
| | MANY OF THE ABOVE COMMENTS REDLINED AND/ |
| | OR CIRCLED FOR LOCATIONS AND ITEMS |
| | MENTIONED IN COMMENTS. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO THREE |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | ABOUT ANY OF THE ABOVE COMMENTS, PLEASE |
| | DO NOT HESITATE IN CONTACTING ME. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |