2007-06-14 10:38:14REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.07 SHOWS A TRENCH DRAIN CONNECTING TO A 4"
 EMERGENCY DRAIN, BUT ALSO TO A 4" DECK DRAIN. SEPARATE
 SYSTEMS ARE REQUIRED PER SECTION 1107.2 AND THE PRIMARY
 DRAIN AND THE SECONDARY DRAINS SHALL NOT CONNECT TO THE
 SAME EMERGENCY DRAIN LINE. PLEASE INDICATE THE REASON
 FOR THE BACKWATER VALVE.
  
 2. SHT P2.07 KEY NOTE #2 INDICATES A 6" SANITARY LINE
 FROM THE FLOOR ABOVE. THE FLOOR ABOVE AND THE FLOOR
 BELOW DO NOT INDICATE A 6" SANITARY LINE IN THIS
 LOCATION. PLEASE CLARIFY. SECTION 104.2.1.
  
 3. SHT P2.07 REVISION 3 BETWEEN COLUMNS 5 & 6 AND
 COLUMNS C & D DOES NOT INDICATE ANY CHANGE FROM
 PREVIOUS REVISION. PLEASE CLARIFY.
  
 4. SHT P2.10 KEY NOTES SHOW NEW NUMBERS 3 THRU 6, BUT
 ARE NOT INDICATED AS REVISIONS WITH CLOUDS OR A
 NUMBERED TRIANGLE. PLEASE INDICATE ALL REVISIONS WITH A
 CLOUD AND A NUMBERED TRIANGLE.
  
 5. SHT P2.105 RWL DESIGNATIONS, (NUMBERS), HAVE BEEN
 REVISED TO BE 3" OR 4" STORM RISERS. PLEASE INDICATE
 WHY THE RWL DESIGNATIONS HAVE BEEN DELETED FROM THIS
 FLOOR. SECTION 104.2.1.
  
 6. SHT P4.14 RISER DIAGRAM SHOWS A TRENCH DRAIN
 CONNECTING TO A 4" EMERGENCY DRAIN, BUT ALSO TO A 4"
 DECK DRAIN. SEPARATE SYSTEMS ARE REQUIRED PER SECTION
 1107.2.REVISION 5 FOR THIS AREA DOES NOT REFLECT THE
 FLOOR PLAN LAYOUT FOR THE DECK DRAIN & PLANTER DRAIN
 SHOWN ON SHT P2.07. THE SQUARE FOOTAGE AND DRAIN
 LAYOUTS ARE DIFFERENT ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS