Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop M
Sequence Number 19
Notes
Date Text
2007-04-25 16:55:24---------------DENIED-------------------
  
 1. M2.01 AND M2.03: GENERATOR EXHAUST PLAN VIEW DOES
 NOT MATCH WHAT IS SHOWN ON ELEVATION VIEW. PLEASE
 COORDINATE DRAWINGS. ALSO, PLEASE PROVIDE INSTALLATION
 INSTRUCTIONS AS NECESSARY TO DETERMINE WHETHER NEW
 EXHAUST DESIGN WILL MEET THE MAX. 2" BACK PRESSURE
 REQUIREMENT.
  
 2. M2.01 AND M2.03: MUST ALSO REVISE THESE PAGES ON
 GENERATOR PERMIT #06041193
  
 3. M3.01: OK
  
 4. M3.01A: WHERE IS 1ST FLOOR LEVEL PLANS FOR THESE
 LOFTS?
  
 5. M3.12: ONLY 2 COPIES PROVIDED. RESUBMIT WITH 3
 COPIES.
  
 6. M3.19 AND M3.20: MISSING FIRE AND/OR SMOKE DAMPERS
 IN SEVERAL LOCATIONS, BOTH PAGES.
  
  