| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
19 |
|
| Notes |
| Date |
Text |
| 2007-04-25 16:55:24 | ---------------DENIED------------------- | | | | | | 1. M2.01 AND M2.03: GENERATOR EXHAUST PLAN VIEW DOES | | | NOT MATCH WHAT IS SHOWN ON ELEVATION VIEW. PLEASE | | | COORDINATE DRAWINGS. ALSO, PLEASE PROVIDE INSTALLATION | | | INSTRUCTIONS AS NECESSARY TO DETERMINE WHETHER NEW | | | EXHAUST DESIGN WILL MEET THE MAX. 2" BACK PRESSURE | | | REQUIREMENT. | | | | | | 2. M2.01 AND M2.03: MUST ALSO REVISE THESE PAGES ON | | | GENERATOR PERMIT #06041193 | | | | | | 3. M3.01: OK | | | | | | 4. M3.01A: WHERE IS 1ST FLOOR LEVEL PLANS FOR THESE | | | LOFTS? | | | | | | 5. M3.12: ONLY 2 COPIES PROVIDED. RESUBMIT WITH 3 | | | COPIES. | | | | | | 6. M3.19 AND M3.20: MISSING FIRE AND/OR SMOKE DAMPERS | | | IN SEVERAL LOCATIONS, BOTH PAGES. | | | | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|