Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop M
Sequence Number 18
Notes
Date Text
2007-03-23 15:38:39NEW SHEETS M3.13-3.18 DUCT LAYOUT FOR 8TH FLOOR
 EXCLUDING CORRIDORS.
  
 ****************PROVISO*****************
  
 RETURN TRANSFERS ARE NOT DESIGNED TO MEET THE
 EXCEPTIONS OF FBC,M 601.4. UNLESS THEY ARE DESIGNED TO
 MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED TO
 VERIFY BALANCED RETURN.
  
 NOTE: SEE PAGES M2.13,M2.14 FOR CORRIDOR DUCT PLAN.
  