| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
18 |
|
| Notes |
| Date |
Text |
| 2007-03-23 15:38:39 | NEW SHEETS M3.13-3.18 DUCT LAYOUT FOR 8TH FLOOR | | | EXCLUDING CORRIDORS. | | | | | | ****************PROVISO***************** | | | | | | RETURN TRANSFERS ARE NOT DESIGNED TO MEET THE | | | EXCEPTIONS OF FBC,M 601.4. UNLESS THEY ARE DESIGNED TO | | | MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED TO | | | VERIFY BALANCED RETURN. | | | | | | NOTE: SEE PAGES M2.13,M2.14 FOR CORRIDOR DUCT PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|