| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
P |
| Sequence Number |
17 |
|
| Notes |
| Date |
Text |
| 2007-05-03 18:49:07 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | SOVENT DESIGN MANUAL NO. 802 | | | | | | 1. SHT P4.02 SOVENT RISERS S/131 & S/133 AN AERATOR IS | | | REQUIRED FOR THE 4" FLOOR DRAIN AT THE TOP OF THE | | | STACK.DESIGN MANUAL PAGE 10 (C) AND PAGE 15 DRAWING | | | 2. | | | | | | 2. SHT P4.02 SOVENT RISER S/96 HAS BEEN DELETED. THIS | | | RISER IS STILL SHOWN ON THE FLOOR PLAN P216. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | | | | 3. SHT P4.04 SOVENT RISER S/110 INDICATES A REVENT FROM | | | RISER S/113. SINCE RISERS S/113 AND S/114 HAVE BEEN | | | CHANGED, THE REVENT DOES NOT CONNECT FROM RISER S/113. | | | PLEASE CORRELATE VENTING INFORMATION. SECTION 104.2.1. | | | | | | 4. SHT P4.04 SOVENT RISER S/111 THE PRL LINE SHALL | | | CONNECT TO THE VERTICAL PORTION OF THE SOVENT STACK, | | | NOT THE HORIZONTAL SECTION AS SHOWN AT THE OFFSET ON | | | THE PENTHOUSE LEVEL. PAGE 18 OF THE DESIGN MANUAL NO. | | | 802. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|