2007-05-03 18:49:07DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 SOVENT DESIGN MANUAL NO. 802
  
 1. SHT P4.02 SOVENT RISERS S/131 & S/133 AN AERATOR IS
 REQUIRED FOR THE 4" FLOOR DRAIN AT THE TOP OF THE
 STACK.DESIGN MANUAL PAGE 10 (C) AND PAGE 15 DRAWING
 2.
  
 2. SHT P4.02 SOVENT RISER S/96 HAS BEEN DELETED. THIS
 RISER IS STILL SHOWN ON THE FLOOR PLAN P216. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 3. SHT P4.04 SOVENT RISER S/110 INDICATES A REVENT FROM
 RISER S/113. SINCE RISERS S/113 AND S/114 HAVE BEEN
 CHANGED, THE REVENT DOES NOT CONNECT FROM RISER S/113.
 PLEASE CORRELATE VENTING INFORMATION. SECTION 104.2.1.
  
 4. SHT P4.04 SOVENT RISER S/111 THE PRL LINE SHALL
 CONNECT TO THE VERTICAL PORTION OF THE SOVENT STACK,
 NOT THE HORIZONTAL SECTION AS SHOWN AT THE OFFSET ON
 THE PENTHOUSE LEVEL. PAGE 18 OF THE DESIGN MANUAL NO.
 802.
  