| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
E |
| Sequence Number |
17 |
|
| Notes |
| Date |
Text |
| 2007-08-01 17:13:55 | ** UNSAT ** | | | | | | | | | 1) NOTE: PLEASE SEE THE REVISED LANDSCAPE PLANS WHICH | | | CONTAIN A SEAL WHICH IS NO LONGER VALID PER | | | FAC61G1-16.002. | | | PLEASE SEE THE ABOVE SECTION FOR THE MINIMUM REQUIRED | | | SEAL. | | | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY | | | OTHER TRADE. | | | | | | 2) NOTE: PLEASE SEE THE BUS-DUCT CURBING DETAIL DOES | | | NOT MEET THE MINIMUM REQUIRED CONSTRUCTION REQUIREMENTS | | | OF THE NEC.368.10C2B (2005), 368.6(2002), 364.6(1999) | | | IF THIS CONSTRUCTION IS DONE IN BUILDING CORRECTIONS | | | WILL BE REQUIRED. | | | PLEASE ALSO SUPPLY DETAIL ON COMPLETE WATERPROOFING FOR | | | COLD JOINTS MADE IN CONCRETE FOR THE FORTH SIDE WHICH | | | WILL BE REQUIRED TO BE ADDED ALONG WITH SEAL BETWEEN | | | CURBING AND FLOORING. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|