| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
P |
| Sequence Number |
14 |
|
| Notes |
| Date |
Text |
| 2007-04-06 07:13:08 | REVISION DENIED | | | REFERENCE FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 FUEL GAS | | | | | | 1. REVISION DENIED SHT P4.01-AN INDIRECT WASTE | | | DOWNSTREAM OF STACK S/100 WHERE STACKS S/98, S/99 & | | | S/100 CONNECT SHOWS A FLOOR SINK WITH NO PIPING TO THE | | | BUILDING DRAIN. SECTION 104.2.1.-THE AIR ADMITTANCE | | | VALVE FOR THE 6" HUB DRAIN REQUIRES A RELIEF VENT PER | | | SECTION 917.3.2.-THE VENT PIPING AT RISER S/5 IS | | | CONNECTING TO THE SANITARY BRANCH LINE. SECTION | | | 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|