Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop P
Sequence Number 11
Notes
Date Text
2007-03-05 18:59:43REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 SOVENT DESIGN MANUAL NO. 802
  
 1. SHT P2.15:
 A. RISERS S/9 & RWL 8 ARE MISLABELED. SECTION
 104.2.1.
 B. RISER S/12 HAS BEEN CHANGED TO S/5. CLARIFY.
 SECTION 104.2.1.
 C. REVISIONS 6,7, & 8 ARE NOT INDICATED
 D. IDENTIFY LINE BEHIND THE LAV IN UNIT B1 2B/2B JUST
 RIGHT OF COL. LINE 8/B. SECTION 104.2.1.
 E. IDENTIFY LINES, (13), AT COL LINE 9 BETWEEN COL'S A
 & B, AND COL LINE A BETWEEN COL'S 9 & 10 AND COL LINE D
 BETWEEN COL 9 & 10. SECTION 104.2.1.
  
 2. SHT P2.16:
 A. RISER S/11 AN AERATOR IS REQUIRED. PAGE 15 DRAWING
 2.
 B. RWL'S 65, 66, & 67. PLEASE INDICATE THE LOCATION OF
 THE RISERS. ONLY THE RISER DESIGNATIONS ARE
 INDICATED.SECTION 104.2.1.
 C. RISER S/59 CONNECTS WHERE? SECTION 104.2.1.
  
 3. SHT P2.17:
 A. WHICH STACK DOES THE VENT ON COL LINE 1 BETWEEN COL
 LINES H & J CONNECT TO? SECTION 104.2.1.
 B. A SECONDARY ROOF DRAIN IS REQUIRED FOR THE ROOF
 AREA TO THE RIGHT OF THE COOLING TOWERS. (3"RD 373SF).
 SECTIONS 1107.1 & 1107.2.
 C. SHOW THE SQUARE FOOTAGE OF THE AREA LEFT OF THE
 STAIRS #36 & SHOW THE LOCATION OF THE SECONDARY ROOF
 DRAIN. WILL THE AREA OF THIS ROOF SECTION DRAIN ONTO
 THE ROOF TERRACE TO THE SOUTH? PLEASE CLARIFY. TABLE
 1106.3 & SECTION 104.2.1.
 D. INDICATE THE SECONDARY ROOF DRAINS FOR ALL
 WALKWAYS. SECTIONS 1107.1 & 1107.2.
 E. CHECK THE ADDITION OF THE SQUARE FOOTAGE FOR THE
 ROOF AREA NORTH OF COL. LINE H/1. SECTION 104.2.1 &
 TABLE 1106.3..
  
 4. SHT P2.18:
 A. A DOOR INTO A PLANTER IS INDICATED RIGHT & SOUTH OF
 THE SPA. (PD 62SF). PLEASE CLARIFY. SECTION 104.2.1.
 B. A SECONDARY DRAIN IS REQUIRED AT ROOF SECTION, (3"
 RD112SF), JUST SOUTH OF STAIR #35. SECTIONS 1107.1 &
 1107.2.
 C. CHECK THE ADDITION FOR (4"RD 981SF) TO THE LEFT OF
 THE MECHANICAL ROOM. SECTION 104.2.1 & TABLE 1106.3.
 D. CHECK THE ADDITION FOR (4"RD 798SF) COL LINE B LEFT
 OF COL LINE 18. SECTION 104.2.1 & TABLE 1106.3.
 E. ROOF DRAIN SHOWN IN THE WALLS OF STAIRS #33 & #34.
 PLEASE CLARIFY. SECTION 104.2.1.
 F. CHECK THE ADDITION FOR THE ROOF DRAINS AT COL LINE
 H BEHIND STAIRS #33 & #34. SECTION 104.2.1 & TABLE
 1106.3.
  
 5. SHT P4.02:
 A. RISERS S/131 & S133 AN AERATOR IS REQUIRED FOR THE
 4"FD. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802.
 B. RISER S/25 IS NOT SHOWN ON SHT P4.05. PLEASE
 CLARIFY. SECTION 104.2.1.
 C. RISER S/24 DOUBLE WASH MACHINES MEZZ. LEVEL.
 INDICATE MAXIMUM 15' FROM THE CENTERLINE OF THE STACK
 TO THE CENTERLINE OF THE MOST REMOTE WASH MACHINE. PAGE
 33 DRAWING #20 SOVENT DESIGN MANUAL 802.
  
 6. SHT P403:
 A. RISER S/42 VENT REQUIRED FOR THE 6" FFD. SECTION
 901.2.1.
 B. A REVISION IS REQUIRED FOR SHT P4.01 SHOWING THE
 CONNECTION OF THE 6" FFD TO A STACK. SECTION 104.2.1.
 C. RISER S/63 2" FLOOR DRAIN CONNECTION IS NOT
 APPROVED AS SHOWN. THIS IS AN "S-TRAP". SECTION
 1002.3(5). TRAP SHALL BE CONNECTED TO THE STACK ABOVE
 THE CEILING.
 D. RISER S/79 FLOOR DRAINS CONNECTION NOT APPROVED. AN
 AERATOR IS REQUIRED PER PAGE 15 DRAWING 2 OF THE SOVENT
 DESIGN MANUAL 802.
  
 7. SHT P404:
 A. RISER 2/110 INDICATES "2 INCH VENT FROM S/113".
 S/113 & S/114 HAVE BEEN CHANGED AND NOW THE 2" VENT IS
 SHOWN CONNECTING TO RISER S/114. PLEASE CORRELATE
 RISERS. SECTION 104.2.1.
  
 8. SHT P4.05:
 A. RISER S/96 AN AERATOR IS REQUIRED FOR THE
 CONNECTION TO THE STACK FROM THE TOILET ROOMS ON THE
 ROOF. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802.
  
 9. SHT P405A:
 A. RISERS S/1, S/2, S/3 - A 5" VENT IS REQUIRED TO
 RISER S/1 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 B. RISERS S/5, S/6 - A 4" VENT IS REQUIRED AFTER THE
 CONNECTION TO S/5 AND THRU THE ROOF. PAGE 42 DETAIL
 A-32.
 C. RISERS S/96, S/97 - A 5" VENT IS REQUIRED THRU THE
 ROOF. THE VENT SHALL TERMINATE 6" ABOVE THE FLOOD RIM
 OF THE HIGHEST FIXTURE. PLEASE INDICATE ON THE PLANS.
 SECTION 905.4.
 D. RISERS S/38, S/43, S/44 - A 4" VENT IS REQUIRED
 AFTER S/43 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 E. RISERS S/98, S/99 - A 4" VENT IS REQUIRED AFTER
 S/98 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 F. RISERS S/59, S/60 - A 5" VENT IS REQUIRED AFTER
 S/60 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 G. RISERS S/84, S/85, S/87, S/128, S/129 - A 5" VENT
 IS REQUIRED AFTER S/128 & THRU THE ROOF. PAGE 42 DETAIL
 A-32.
 H. RISERS S/110, S/112 DO NOT REFLECT THE FLOOR PLAN.
 ALSO INDICATE WHAT STACK THE KITCHEN SINK VENT COMES
 FROM. SECTION 104..2.1.
 I. RISERS S/119, S/120, S/123 - A 5" VENT IS REQUIRED
 AFTER THE CONNECTION FROM RISERS S/119 & S/120 & THRU
 THE ROOF. PAGE 42 DETAIL A-32.
  
 INFORMATIONAL: SEE RED LINE MARK-UPS ON ONE SET OF
 PLANS. THIS WILL HELP IDENTIFY AREAS OF COMMENT. PLEASE
 RETURN THIS SET TO HELP EXPEDITE THE REVIEW PROCESS
 WHEN THE REVISIONS ARE RESUBMITTED FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. ALSO PLEASE
 SUBMIT THE SHEETS WITH RED LINE REMARKS TO
 HELP EXPEDITE THE REVIEW.THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  