Text |
| 2007-03-05 18:59:43 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | SOVENT DESIGN MANUAL NO. 802 |
| | |
| | 1. SHT P2.15: |
| | A. RISERS S/9 & RWL 8 ARE MISLABELED. SECTION |
| | 104.2.1. |
| | B. RISER S/12 HAS BEEN CHANGED TO S/5. CLARIFY. |
| | SECTION 104.2.1. |
| | C. REVISIONS 6,7, & 8 ARE NOT INDICATED |
| | D. IDENTIFY LINE BEHIND THE LAV IN UNIT B1 2B/2B JUST |
| | RIGHT OF COL. LINE 8/B. SECTION 104.2.1. |
| | E. IDENTIFY LINES, (13), AT COL LINE 9 BETWEEN COL'S A |
| | & B, AND COL LINE A BETWEEN COL'S 9 & 10 AND COL LINE D |
| | BETWEEN COL 9 & 10. SECTION 104.2.1. |
| | |
| | 2. SHT P2.16: |
| | A. RISER S/11 AN AERATOR IS REQUIRED. PAGE 15 DRAWING |
| | 2. |
| | B. RWL'S 65, 66, & 67. PLEASE INDICATE THE LOCATION OF |
| | THE RISERS. ONLY THE RISER DESIGNATIONS ARE |
| | INDICATED.SECTION 104.2.1. |
| | C. RISER S/59 CONNECTS WHERE? SECTION 104.2.1. |
| | |
| | 3. SHT P2.17: |
| | A. WHICH STACK DOES THE VENT ON COL LINE 1 BETWEEN COL |
| | LINES H & J CONNECT TO? SECTION 104.2.1. |
| | B. A SECONDARY ROOF DRAIN IS REQUIRED FOR THE ROOF |
| | AREA TO THE RIGHT OF THE COOLING TOWERS. (3"RD 373SF). |
| | SECTIONS 1107.1 & 1107.2. |
| | C. SHOW THE SQUARE FOOTAGE OF THE AREA LEFT OF THE |
| | STAIRS #36 & SHOW THE LOCATION OF THE SECONDARY ROOF |
| | DRAIN. WILL THE AREA OF THIS ROOF SECTION DRAIN ONTO |
| | THE ROOF TERRACE TO THE SOUTH? PLEASE CLARIFY. TABLE |
| | 1106.3 & SECTION 104.2.1. |
| | D. INDICATE THE SECONDARY ROOF DRAINS FOR ALL |
| | WALKWAYS. SECTIONS 1107.1 & 1107.2. |
| | E. CHECK THE ADDITION OF THE SQUARE FOOTAGE FOR THE |
| | ROOF AREA NORTH OF COL. LINE H/1. SECTION 104.2.1 & |
| | TABLE 1106.3.. |
| | |
| | 4. SHT P2.18: |
| | A. A DOOR INTO A PLANTER IS INDICATED RIGHT & SOUTH OF |
| | THE SPA. (PD 62SF). PLEASE CLARIFY. SECTION 104.2.1. |
| | B. A SECONDARY DRAIN IS REQUIRED AT ROOF SECTION, (3" |
| | RD112SF), JUST SOUTH OF STAIR #35. SECTIONS 1107.1 & |
| | 1107.2. |
| | C. CHECK THE ADDITION FOR (4"RD 981SF) TO THE LEFT OF |
| | THE MECHANICAL ROOM. SECTION 104.2.1 & TABLE 1106.3. |
| | D. CHECK THE ADDITION FOR (4"RD 798SF) COL LINE B LEFT |
| | OF COL LINE 18. SECTION 104.2.1 & TABLE 1106.3. |
| | E. ROOF DRAIN SHOWN IN THE WALLS OF STAIRS #33 & #34. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | F. CHECK THE ADDITION FOR THE ROOF DRAINS AT COL LINE |
| | H BEHIND STAIRS #33 & #34. SECTION 104.2.1 & TABLE |
| | 1106.3. |
| | |
| | 5. SHT P4.02: |
| | A. RISERS S/131 & S133 AN AERATOR IS REQUIRED FOR THE |
| | 4"FD. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802. |
| | B. RISER S/25 IS NOT SHOWN ON SHT P4.05. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | C. RISER S/24 DOUBLE WASH MACHINES MEZZ. LEVEL. |
| | INDICATE MAXIMUM 15' FROM THE CENTERLINE OF THE STACK |
| | TO THE CENTERLINE OF THE MOST REMOTE WASH MACHINE. PAGE |
| | 33 DRAWING #20 SOVENT DESIGN MANUAL 802. |
| | |
| | 6. SHT P403: |
| | A. RISER S/42 VENT REQUIRED FOR THE 6" FFD. SECTION |
| | 901.2.1. |
| | B. A REVISION IS REQUIRED FOR SHT P4.01 SHOWING THE |
| | CONNECTION OF THE 6" FFD TO A STACK. SECTION 104.2.1. |
| | C. RISER S/63 2" FLOOR DRAIN CONNECTION IS NOT |
| | APPROVED AS SHOWN. THIS IS AN "S-TRAP". SECTION |
| | 1002.3(5). TRAP SHALL BE CONNECTED TO THE STACK ABOVE |
| | THE CEILING. |
| | D. RISER S/79 FLOOR DRAINS CONNECTION NOT APPROVED. AN |
| | AERATOR IS REQUIRED PER PAGE 15 DRAWING 2 OF THE SOVENT |
| | DESIGN MANUAL 802. |
| | |
| | 7. SHT P404: |
| | A. RISER 2/110 INDICATES "2 INCH VENT FROM S/113". |
| | S/113 & S/114 HAVE BEEN CHANGED AND NOW THE 2" VENT IS |
| | SHOWN CONNECTING TO RISER S/114. PLEASE CORRELATE |
| | RISERS. SECTION 104.2.1. |
| | |
| | 8. SHT P4.05: |
| | A. RISER S/96 AN AERATOR IS REQUIRED FOR THE |
| | CONNECTION TO THE STACK FROM THE TOILET ROOMS ON THE |
| | ROOF. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802. |
| | |
| | 9. SHT P405A: |
| | A. RISERS S/1, S/2, S/3 - A 5" VENT IS REQUIRED TO |
| | RISER S/1 & THRU THE ROOF. PAGE 42 DETAIL A-32. |
| | B. RISERS S/5, S/6 - A 4" VENT IS REQUIRED AFTER THE |
| | CONNECTION TO S/5 AND THRU THE ROOF. PAGE 42 DETAIL |
| | A-32. |
| | C. RISERS S/96, S/97 - A 5" VENT IS REQUIRED THRU THE |
| | ROOF. THE VENT SHALL TERMINATE 6" ABOVE THE FLOOD RIM |
| | OF THE HIGHEST FIXTURE. PLEASE INDICATE ON THE PLANS. |
| | SECTION 905.4. |
| | D. RISERS S/38, S/43, S/44 - A 4" VENT IS REQUIRED |
| | AFTER S/43 & THRU THE ROOF. PAGE 42 DETAIL A-32. |
| | E. RISERS S/98, S/99 - A 4" VENT IS REQUIRED AFTER |
| | S/98 & THRU THE ROOF. PAGE 42 DETAIL A-32. |
| | F. RISERS S/59, S/60 - A 5" VENT IS REQUIRED AFTER |
| | S/60 & THRU THE ROOF. PAGE 42 DETAIL A-32. |
| | G. RISERS S/84, S/85, S/87, S/128, S/129 - A 5" VENT |
| | IS REQUIRED AFTER S/128 & THRU THE ROOF. PAGE 42 DETAIL |
| | A-32. |
| | H. RISERS S/110, S/112 DO NOT REFLECT THE FLOOR PLAN. |
| | ALSO INDICATE WHAT STACK THE KITCHEN SINK VENT COMES |
| | FROM. SECTION 104..2.1. |
| | I. RISERS S/119, S/120, S/123 - A 5" VENT IS REQUIRED |
| | AFTER THE CONNECTION FROM RISERS S/119 & S/120 & THRU |
| | THE ROOF. PAGE 42 DETAIL A-32. |
| | |
| | INFORMATIONAL: SEE RED LINE MARK-UPS ON ONE SET OF |
| | PLANS. THIS WILL HELP IDENTIFY AREAS OF COMMENT. PLEASE |
| | RETURN THIS SET TO HELP EXPEDITE THE REVIEW PROCESS |
| | WHEN THE REVISIONS ARE RESUBMITTED FOR REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. ALSO PLEASE |
| | SUBMIT THE SHEETS WITH RED LINE REMARKS TO |
| | HELP EXPEDITE THE REVIEW.THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |