| Plan Review Notes For Permit 04031591 |
| Permit Number |
04031591 |
|
| Review Stop |
M |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2006-03-01 00:00:00 | PROVISO: | | | REVISION; PLAN SHEETS M2.01, M2.03, AND | | | M5.02 | | | | | | 1.PLAN SHEET M2.01, PLEASE LOCATE | | | FRESH AIR INTAKES TO THE FIRE PUMP ROOM | | | AND THE SWITCHGEAR ROOMS AS HIGH AS | | | POSSIBLE.PER 2001 FBC 401.5.1, INTAKE | | | OPENINGS SHALL BE LOCATED A MINIMUM OF | | | 10 FT FROM NOXIOUS CONTAMINANTS SUCH AS | | | LOADING DOCKS.PLEASE ALSO PROVIDE CO | | | SENSORS IN THESE ROOMS. | | | | | | 2.PLEASE NOTE, THE TERMINATION OF THE | | | MUFFLER EXHAUST FROM THE GENERATOR SHALL | | | COMPLY WITH 2005 NFPA 110 CHAPTER 7 | | | SECTION 7.10.2, EXHAUST SYSTEM SHALL | | | TERMINATE IN SUCH A MANNER THAT TOXIC | | | FUMES CONNOT REENTER A BUILDING OR | | | STRUCTURE THROUGH WINDOWS, AIR | | | VETILATION INTLETS OR THE ENGINE AIR | | | INTAKE SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|