Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-24 00:00:00PLAN REVIEW DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT A1.14 SECONDARY DRAINS FOR ROOF
 DRAINS AND FOR FLOOR DRAINS AT TERRACES
 ARE NOT SHOWN. PLEASE SHOW ALL SECONDARY
 DRAINS. SECTION 104.2.1
 2) SHTS A1.15, A1.16, & A1.17 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106, AND 1107
 WITH ALL SUBSECTIONS. SHOW SQUARE FEET
 FOR EACH SECTION, ADDED 1/2 AREA FOR ALL
 VERTICAL WALLS INCLUDING PARAPETS, ALL
 SQUARE FEET FOR ALL ROOFS THAT DRAIN TO
 ROOF FROM ABOVE. SHOW LOCATION OF ALL
 SECONDARY ROOF DRAINS.
 3) SHT A1.17 ROOF SCUPPER DETAIL #7 AND
 DETAIL #4 NO HEIGHT AND WIDTH SHOWN ON
 DETAILS.
 4) SHT A9.0 BACKING NOT SHOWN FOR THE
 FOOT OF THE TUB, AND NO BACKING SHOWN
 FOR THE SHOWER.
 5) SHT A9.1 DETAILS A,C, & E INDICATE
 THE HEIGHT FOR W/C, & LAV. SHOW FLUSH
 CONTROL PER CHAPTER 11, SECTIONS 4.16.3,
 4.19.2, AND 4.16.5.
 6) SHT A9.1 DETAILS B, D, & F INDICATE
 MEASUREMENT TO CENTERLINE OF FIXTURES
 OFF WALL FOR WATER CLOSET AND LAV.
 7) SHTS A9.2 THRU A9.35 ALL LOFTS, INDI-
 CATE MEASUREMENTS TO CENTERLINE OF FIX-
 TURES FOR W/C AND LAV OFF WALL FOR ACC-
 ESSIBLE TOILET ROOMS, HEIGHT OF LAVS AND
 W/C, FLUSH CONTROL. (SEE COMMENT #5).
 8) SHTS A9.4 THRU A9.15 SHOW CLEAR FLOOR
 SPACE FOR ALL REQUIRED BATHROOM FIXTURES
 PER PAGES 7.43, 7.47, & 7.53 OF THE FHA
 DESIGN MANUAL.
 9) SHTS A9.4 THRU A9.15 WHERE APPLICABLE
 CORRECT THE FOLLOWING ISSUES:
 A) ALL LAVS WITH PARALLEL APPROACH, THE
 LAV SHALL BE CENTERED ON THE 48" SIDE OF
 THE CLEAR FLOOR SPACE AND SHALL BE A MIN
 OF 2' OFF WALL OR 30" OFF ADJACENT FIX-
 TURE.
 B) INTERIOR ELEVATION SHALL REFLECT THE
 KEY PLAN WHEN SHOWING MEASUREMENTS FOR
 THE CENTERLINE OF THE TOILET OFF THE
 WALL OR ADJACENT FIXTURES/VANITY.
 C) UNITS WITH SPECIFICATION "B" SHOW
 CLEAR FLOOR SPACE IN EACH BATHROOM. IN-
 DICATE WHICH BATHROOM WILL COMPLY AND
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES.
 D) THE 18" FROM THE CENTERLINE OF THE
 W/C TO THE WALL IS AN ABSOLUTE MEASUR-
 MENT. SEE PAGE 6.5
 E) SOME UNITS DO NOT SHOW AN ELEVATION
 FOR THE WATER CLOSET. IF THE BATHROOM
 TO BE DESIGNATED TO COMPLY DOES NOT HAVE
 AN ELEVATION FOR THE W/C, PLEASE SUBMIT
 THE ELEVATION.
 10) ALL PLUMBING SHEETS, THE CERTIFICATE
 OF AUTHROIZATION IS REQUIRED ON THE
 TITLE BLOCK PER FAC 61G15-23.002(2) -
 FS 471.025.
 11) SHTS P2.01 & P2.02 WATER DISTRIBUT-
 ION LINE SHOWS THE PUMP PRESSURE OUT OF
 THE DOMESTIC PUMP, BUT THEN DROPS DOWN
 TO STREET PRESSURE AND THEN BACK UP TO
 PUMP PRESSURE. PLEASE CLARIFY. SECTION
 104.2.1
 12) SHT P4.01 SANT. COLLECTION ISOMETRIC
 SHOW PIPE SIZE AND DFU'S AS THEY ACCUMU-
 LATE IN THE SYSTEM.
 13) SHT P4.08 DETAIL #1 SHOWS 2 WASH
 MACHINES. PLEASE CLARIFY. SEC 104.2.1.
 14) NO WATER ISOMETRICS FOR UNITS "B4",
 "B7", OR "TH-1" (L-8).
 15) SHT P4.12:
 DETAIL #1 NO WATER SUPPLY SHOWN FOR LAVS
 OR TUB/SHOWER.
 DETAIL #2 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM.
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM.
 16) SHTS P4.13 AND P4.14 STORM COLLECT-
 ION ISOMETRIC, INDICATE PIPE SIZE AND
 SHOW SQUARE FEET AS THEY ACCUMULATE IN
 THE SYSYTE. TABLES 1106.2 AND 1106.3.
 17) SUBMIT CONDENSATE RISER DIAGRAMS AND
 A CONDENSATE COLLECTION ISOMETRIC SHOW-
 ING ALL PIPE SIZES AND TERMINATION POINT
 FOR CONDENSATE. SECTION 104.2.1
 18) SHTS P2.13 & P2.14 SHOW WATER DIST.
 TO BE IN THE CEILING OF THE 7TH FLOOR.
 SHT P407 INDICATES WATER DIST. PIPING TO
 BE IN 8TH FLOOR CEILING. PLEASE CLARIFY.
 SECTION 104.2.1
 19) TRASH CHUTE WASH DOWN LINE ARE NOT
 SHOWN. BACKFLOW PROTECTION REQUIRED FOR
 THESE LINES.
 20) SWIMMING POOL FILL LINE NOT SHOW.
 BACKFLOW PROTECTION REQUIRED FOR THIS
 LINE.
 21) BACKFLOW PROTECTION REQUIRED FOR
 WATER SUPPLY LINE TO COOLING TOWER.
 SUBMIT DETAIL SHOWING PROTECTION.
 22) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR APPLICATION FOR SEPARATE GAS PER-
 MIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G) IF WELDED PIPE PRIOR TO ISSUING GAS
 PERMIT, THE WELDER SHALL PROVIDE A PICT-
 URE IDENTIFICATION, WELDING CERTIFICAT-
 ION AND WELDING PROCEDURE.
 23) SUBMIT DESIGN MANUAL 101 REFERENCED
 ON SHEET P5.02. SECTION 104.2.1
 24) SHOW APPROVAL FOR SYSTEM BY AN APP-
 ROVED TESTING AGENCY. SHOW TESTING FOR
 FLOW RATES. SECTION 104.2.1.2
 25) MANY RISERS DO NOT COMPLY WITH THE
 REQUIREMENTS INDICATED ON SHEET P5.08
 SECTION 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A SET
 OF PLUMBING PLANS HAS BEEN HIGHLIGHTED
 DURING REVIEW AND IF POSSIBLE THIS SET
 SHOULD BE RETURNED. THIS WILL HELP TO
 EXPIDITE THE NEXT PLUMBING REVIEW. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved