| Date |
Text |
| 2004-04-24 00:00:00 | PLAN REVIEW DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1) SHT A1.14 SECONDARY DRAINS FOR ROOF |
| | DRAINS AND FOR FLOOR DRAINS AT TERRACES |
| | ARE NOT SHOWN. PLEASE SHOW ALL SECONDARY |
| | DRAINS. SECTION 104.2.1 |
| | 2) SHTS A1.15, A1.16, & A1.17 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS PER SECTIONS 1106, AND 1107 |
| | WITH ALL SUBSECTIONS. SHOW SQUARE FEET |
| | FOR EACH SECTION, ADDED 1/2 AREA FOR ALL |
| | VERTICAL WALLS INCLUDING PARAPETS, ALL |
| | SQUARE FEET FOR ALL ROOFS THAT DRAIN TO |
| | ROOF FROM ABOVE. SHOW LOCATION OF ALL |
| | SECONDARY ROOF DRAINS. |
| | 3) SHT A1.17 ROOF SCUPPER DETAIL #7 AND |
| | DETAIL #4 NO HEIGHT AND WIDTH SHOWN ON |
| | DETAILS. |
| | 4) SHT A9.0 BACKING NOT SHOWN FOR THE |
| | FOOT OF THE TUB, AND NO BACKING SHOWN |
| | FOR THE SHOWER. |
| | 5) SHT A9.1 DETAILS A,C, & E INDICATE |
| | THE HEIGHT FOR W/C, & LAV. SHOW FLUSH |
| | CONTROL PER CHAPTER 11, SECTIONS 4.16.3, |
| | 4.19.2, AND 4.16.5. |
| | 6) SHT A9.1 DETAILS B, D, & F INDICATE |
| | MEASUREMENT TO CENTERLINE OF FIXTURES |
| | OFF WALL FOR WATER CLOSET AND LAV. |
| | 7) SHTS A9.2 THRU A9.35 ALL LOFTS, INDI- |
| | CATE MEASUREMENTS TO CENTERLINE OF FIX- |
| | TURES FOR W/C AND LAV OFF WALL FOR ACC- |
| | ESSIBLE TOILET ROOMS, HEIGHT OF LAVS AND |
| | W/C, FLUSH CONTROL. (SEE COMMENT #5). |
| | 8) SHTS A9.4 THRU A9.15 SHOW CLEAR FLOOR |
| | SPACE FOR ALL REQUIRED BATHROOM FIXTURES |
| | PER PAGES 7.43, 7.47, & 7.53 OF THE FHA |
| | DESIGN MANUAL. |
| | 9) SHTS A9.4 THRU A9.15 WHERE APPLICABLE |
| | CORRECT THE FOLLOWING ISSUES: |
| | A) ALL LAVS WITH PARALLEL APPROACH, THE |
| | LAV SHALL BE CENTERED ON THE 48" SIDE OF |
| | THE CLEAR FLOOR SPACE AND SHALL BE A MIN |
| | OF 2' OFF WALL OR 30" OFF ADJACENT FIX- |
| | TURE. |
| | B) INTERIOR ELEVATION SHALL REFLECT THE |
| | KEY PLAN WHEN SHOWING MEASUREMENTS FOR |
| | THE CENTERLINE OF THE TOILET OFF THE |
| | WALL OR ADJACENT FIXTURES/VANITY. |
| | C) UNITS WITH SPECIFICATION "B" SHOW |
| | CLEAR FLOOR SPACE IN EACH BATHROOM. IN- |
| | DICATE WHICH BATHROOM WILL COMPLY AND |
| | SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED |
| | FIXTURES. |
| | D) THE 18" FROM THE CENTERLINE OF THE |
| | W/C TO THE WALL IS AN ABSOLUTE MEASUR- |
| | MENT. SEE PAGE 6.5 |
| | E) SOME UNITS DO NOT SHOW AN ELEVATION |
| | FOR THE WATER CLOSET. IF THE BATHROOM |
| | TO BE DESIGNATED TO COMPLY DOES NOT HAVE |
| | AN ELEVATION FOR THE W/C, PLEASE SUBMIT |
| | THE ELEVATION. |
| | 10) ALL PLUMBING SHEETS, THE CERTIFICATE |
| | OF AUTHROIZATION IS REQUIRED ON THE |
| | TITLE BLOCK PER FAC 61G15-23.002(2) - |
| | FS 471.025. |
| | 11) SHTS P2.01 & P2.02 WATER DISTRIBUT- |
| | ION LINE SHOWS THE PUMP PRESSURE OUT OF |
| | THE DOMESTIC PUMP, BUT THEN DROPS DOWN |
| | TO STREET PRESSURE AND THEN BACK UP TO |
| | PUMP PRESSURE. PLEASE CLARIFY. SECTION |
| | 104.2.1 |
| | 12) SHT P4.01 SANT. COLLECTION ISOMETRIC |
| | SHOW PIPE SIZE AND DFU'S AS THEY ACCUMU- |
| | LATE IN THE SYSTEM. |
| | 13) SHT P4.08 DETAIL #1 SHOWS 2 WASH |
| | MACHINES. PLEASE CLARIFY. SEC 104.2.1. |
| | 14) NO WATER ISOMETRICS FOR UNITS "B4", |
| | "B7", OR "TH-1" (L-8). |
| | 15) SHT P4.12: |
| | DETAIL #1 NO WATER SUPPLY SHOWN FOR LAVS |
| | OR TUB/SHOWER. |
| | DETAIL #2 DOES NOT REFLECT THE FLOOR |
| | PLAN AT SECOND BATHROOM. |
| | DETAIL #4 DOES NOT REFLECT THE FLOOR |
| | PLAN AT SECOND BATHROOM. |
| | 16) SHTS P4.13 AND P4.14 STORM COLLECT- |
| | ION ISOMETRIC, INDICATE PIPE SIZE AND |
| | SHOW SQUARE FEET AS THEY ACCUMULATE IN |
| | THE SYSYTE. TABLES 1106.2 AND 1106.3. |
| | 17) SUBMIT CONDENSATE RISER DIAGRAMS AND |
| | A CONDENSATE COLLECTION ISOMETRIC SHOW- |
| | ING ALL PIPE SIZES AND TERMINATION POINT |
| | FOR CONDENSATE. SECTION 104.2.1 |
| | 18) SHTS P2.13 & P2.14 SHOW WATER DIST. |
| | TO BE IN THE CEILING OF THE 7TH FLOOR. |
| | SHT P407 INDICATES WATER DIST. PIPING TO |
| | BE IN 8TH FLOOR CEILING. PLEASE CLARIFY. |
| | SECTION 104.2.1 |
| | 19) TRASH CHUTE WASH DOWN LINE ARE NOT |
| | SHOWN. BACKFLOW PROTECTION REQUIRED FOR |
| | THESE LINES. |
| | 20) SWIMMING POOL FILL LINE NOT SHOW. |
| | BACKFLOW PROTECTION REQUIRED FOR THIS |
| | LINE. |
| | 21) BACKFLOW PROTECTION REQUIRED FOR |
| | WATER SUPPLY LINE TO COOLING TOWER. |
| | SUBMIT DETAIL SHOWING PROTECTION. |
| | 22) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR APPLICATION FOR SEPARATE GAS PER- |
| | MIT REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G) IF WELDED PIPE PRIOR TO ISSUING GAS |
| | PERMIT, THE WELDER SHALL PROVIDE A PICT- |
| | URE IDENTIFICATION, WELDING CERTIFICAT- |
| | ION AND WELDING PROCEDURE. |
| | 23) SUBMIT DESIGN MANUAL 101 REFERENCED |
| | ON SHEET P5.02. SECTION 104.2.1 |
| | 24) SHOW APPROVAL FOR SYSTEM BY AN APP- |
| | ROVED TESTING AGENCY. SHOW TESTING FOR |
| | FLOW RATES. SECTION 104.2.1.2 |
| | 25) MANY RISERS DO NOT COMPLY WITH THE |
| | REQUIREMENTS INDICATED ON SHEET P5.08 |
| | SECTION 104.2.1 |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A SET |
| | OF PLUMBING PLANS HAS BEEN HIGHLIGHTED |
| | DURING REVIEW AND IF POSSIBLE THIS SET |
| | SHOULD BE RETURNED. THIS WILL HELP TO |
| | EXPIDITE THE NEXT PLUMBING REVIEW. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |