2004-04-29 00:00:00DENIED:
 1.PLAN SHEET M2.01, SMOKE CONTROL
 NOTE INDICATES COMPLAINCE WITH 412.5 #1
 OF THE 2001 FBC, SUCH WINDOWS, PANELS &
 CONTROLS SHALL BE CLEARLY IDENTIFIED ON
 THE PLAN.
  
 2.2001 FBC(M) 401.5, OUTSIDE AIR
 EXHAUST AND INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOT LINES.
 OPENINGS THAT ARE AJACENT TO THE STREET
 OR PUBLIC WAY SHALL BE MEASURED FROM
 THE CENTERLINE OF THE STREET.PLEASE
 NOTE, EXHAUST OPENING SHALL BE SITUATED
 AS NOT RECIRCULATE INTO THE FRESH AIR
 INTAKES.
  
 3.PLEASE CLARIFY 96" X 96" LOUVER
 LOCATED BY THE LOADING DOCK.IS IT THE
 INTENT OF THIS LOUVER SUPPLYING MAKE-UP
 AIR INTO THE GARAGE OR EXHAUST, PLEASE
 CLARIFY.2001 FBC(M) 501.3 & 401.5.1.
  
 4.CLARIFY FUNCTION OF CF0.9.
  
 5.OPENINGS TO THE ALLEY - PROTECTION
 THROUGH A RATED ASSEMBLY,PLEASE
 CLARIFY.REFERENCE 2001 FBC 705.1
 THROUGH 705.1.1.4.SEE ALSO COMMENT #5
 BY ASST FIRE MARSHALL, MIKE CARSILLO.
  
 6.PLAN SHEET M2.01 30" X 10" DUCT
 TEMINATING ABOVE THE DOOR (O.A.?),
 PLEASE CLARIFY RATING OF THIS WALL.
  
 7.PLAN SHEET M2.03, NOTE LOCATION OF
 INTAKE LOUVERS IN RELATION WITH
 SEF0.10.PER 2001 FBC(M) 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM NOXIOUS OR
 HAZARDOUS CONTAMINANT.
  
 8.PLAN SHEET M2.08 & DETAIL ON PLAN
 SHEET M6.04 DRYER EXHAUST, PLAN
 INDICATES THE BOTTOM OF THE SHAFT
 TERMINATING IN THE GARAGE.PLANS DO
 NOT INDICATE CLEANOUTS AS REQUIRED PER
 2001 FBC(M) 505.3. DRYER EXHAUST SHALL
 NOT PENETRATE FIRE RATED ASSEMBLIES PER
 2001 FBC(M) 504.2.FIRE DAMPERS LOCATED
 AT THE BOTTOM OF THE SHAFT ARE NOT
 ACCEPTABLE.
  
 9.DRYER EXHAUST SHAFT SHALL COMPLY
 WITH NFPA 13 SUB-SECTION 8.14.2.
  
 10. SHEET M2.14, 10" CONDENSER WATER
 SUPPLY AND RETURN FROM ROOF.PER 2001
 FBC(M) 1206.1.1, IN A HYDRONIC SYSTEM,
 FLUID SHALL NOT ENTER THE TEE THROUGH
 THE BRANCH SIDE.
  
 10. PLAN SHEET M3.01 KEYNOTES #1 INLINE
 BOOSTER FAN, PROVIDE SUBMITTAL & UL
 LISTING.PROVIDE INFORMATION AS TO
 STEPS TAKEN SHOULD BOOSTER FAN FAIL?
  
 11. PLAN SHEET M8.01 SMOKE CONTROL
 PLEASE INDICATE IF THE ELEVATOR SHAFTS
 WILL PRESSURIZE.
  
 12. PLAN SHEET M8.02 DETAIL INDICATES
 CORRIDOR EXHAUST WHEREAS PLAN M2.01
 INDICATES COMPLIANCE BY WINDOWS AND
 PANELS (412.5 #1). PLEASE CLARIFY.
  
 13. O.A. REQUIREMENTS FOR THE CONDO
 UNITS, PROVIDE TEST DATA FROM THE
 MANUFACTURER SHOWING "ACTUALS" FOR THE
 RATE OF FILTRATION.PROVIDE THIS
 INFORMATION FOR EACH WINDOW & DOOR FOR
 EACH UNIT.
  
 14.O.A. SCHEDULE DOES NOT INDICATE
 THAT UNITS MEET THE REQUIREMENT AS
 LISTED ON THE SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.