| Date |
Text |
| 2004-04-29 00:00:00 | DENIED: |
| | 1.PLAN SHEET M2.01, SMOKE CONTROL |
| | NOTE INDICATES COMPLAINCE WITH 412.5 #1 |
| | OF THE 2001 FBC, SUCH WINDOWS, PANELS & |
| | CONTROLS SHALL BE CLEARLY IDENTIFIED ON |
| | THE PLAN. |
| | |
| | 2.2001 FBC(M) 401.5, OUTSIDE AIR |
| | EXHAUST AND INTAKES SHALL BE LOCATED A |
| | MINIMUM OF 10 FT FROM LOT LINES. |
| | OPENINGS THAT ARE AJACENT TO THE STREET |
| | OR PUBLIC WAY SHALL BE MEASURED FROM |
| | THE CENTERLINE OF THE STREET.PLEASE |
| | NOTE, EXHAUST OPENING SHALL BE SITUATED |
| | AS NOT RECIRCULATE INTO THE FRESH AIR |
| | INTAKES. |
| | |
| | 3.PLEASE CLARIFY 96" X 96" LOUVER |
| | LOCATED BY THE LOADING DOCK.IS IT THE |
| | INTENT OF THIS LOUVER SUPPLYING MAKE-UP |
| | AIR INTO THE GARAGE OR EXHAUST, PLEASE |
| | CLARIFY.2001 FBC(M) 501.3 & 401.5.1. |
| | |
| | 4.CLARIFY FUNCTION OF CF0.9. |
| | |
| | 5.OPENINGS TO THE ALLEY - PROTECTION |
| | THROUGH A RATED ASSEMBLY,PLEASE |
| | CLARIFY.REFERENCE 2001 FBC 705.1 |
| | THROUGH 705.1.1.4.SEE ALSO COMMENT #5 |
| | BY ASST FIRE MARSHALL, MIKE CARSILLO. |
| | |
| | 6.PLAN SHEET M2.01 30" X 10" DUCT |
| | TEMINATING ABOVE THE DOOR (O.A.?), |
| | PLEASE CLARIFY RATING OF THIS WALL. |
| | |
| | 7.PLAN SHEET M2.03, NOTE LOCATION OF |
| | INTAKE LOUVERS IN RELATION WITH |
| | SEF0.10.PER 2001 FBC(M) 401.5.1, |
| | INTAKE OPENINGS SHALL BE LOCATED A |
| | MINIMUM OF 10 FT FROM NOXIOUS OR |
| | HAZARDOUS CONTAMINANT. |
| | |
| | 8.PLAN SHEET M2.08 & DETAIL ON PLAN |
| | SHEET M6.04 DRYER EXHAUST, PLAN |
| | INDICATES THE BOTTOM OF THE SHAFT |
| | TERMINATING IN THE GARAGE.PLANS DO |
| | NOT INDICATE CLEANOUTS AS REQUIRED PER |
| | 2001 FBC(M) 505.3. DRYER EXHAUST SHALL |
| | NOT PENETRATE FIRE RATED ASSEMBLIES PER |
| | 2001 FBC(M) 504.2.FIRE DAMPERS LOCATED |
| | AT THE BOTTOM OF THE SHAFT ARE NOT |
| | ACCEPTABLE. |
| | |
| | 9.DRYER EXHAUST SHAFT SHALL COMPLY |
| | WITH NFPA 13 SUB-SECTION 8.14.2. |
| | |
| | 10. SHEET M2.14, 10" CONDENSER WATER |
| | SUPPLY AND RETURN FROM ROOF.PER 2001 |
| | FBC(M) 1206.1.1, IN A HYDRONIC SYSTEM, |
| | FLUID SHALL NOT ENTER THE TEE THROUGH |
| | THE BRANCH SIDE. |
| | |
| | 10. PLAN SHEET M3.01 KEYNOTES #1 INLINE |
| | BOOSTER FAN, PROVIDE SUBMITTAL & UL |
| | LISTING.PROVIDE INFORMATION AS TO |
| | STEPS TAKEN SHOULD BOOSTER FAN FAIL? |
| | |
| | 11. PLAN SHEET M8.01 SMOKE CONTROL |
| | PLEASE INDICATE IF THE ELEVATOR SHAFTS |
| | WILL PRESSURIZE. |
| | |
| | 12. PLAN SHEET M8.02 DETAIL INDICATES |
| | CORRIDOR EXHAUST WHEREAS PLAN M2.01 |
| | INDICATES COMPLIANCE BY WINDOWS AND |
| | PANELS (412.5 #1). PLEASE CLARIFY. |
| | |
| | 13. O.A. REQUIREMENTS FOR THE CONDO |
| | UNITS, PROVIDE TEST DATA FROM THE |
| | MANUFACTURER SHOWING "ACTUALS" FOR THE |
| | RATE OF FILTRATION.PROVIDE THIS |
| | INFORMATION FOR EACH WINDOW & DOOR FOR |
| | EACH UNIT. |
| | |
| | 14.O.A. SCHEDULE DOES NOT INDICATE |
| | THAT UNITS MEET THE REQUIREMENT AS |
| | LISTED ON THE SCHEDULE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |