| 2004-04-01 00:00:00 | 1) SITE PLAN DOES NOT DISPLAY ANY |
| | EXISTING OR NEW FIRE HYDRANTS. |
| | |
| | 2) EXIT STAIRS ARE REQUIRED TO BE |
| | KEPT UP WITH CONSTRUCTION. |
| | |
| | 3) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE |
| | STORIES OR 30 FEET IN HEIGHT. |
| | |
| | 4) PLEASE EXPLAIN HOW ALL OF THE |
| | REQUIRED EQUIPMENT OF THE FBC, SECTION |
| | 412 ARE EXPECTED TO FIT INTO THE |
| | SMALL COMMAND ROOM. |
| | |
| | 5) HOW WILL EXIT DISCHARGE LOCATIONS |
| | BE MAINTAINED IN THE ALLEY. BY THE WAY |
| | WHO'S PROPERTY IS THE ALLEY. |
| | |
| | 6) PLEASE INDICATE WHICH ELEVATORS |
| | WILL BE STRETCHER ACCESSIBLE. |
| | |
| | 7) AN EXIT DISCHARGE LINE GOES |
| | THROUGH THE LOADING DOCK. |
| | |
| | 8) THE TRAVEL DISTANCE LINE ON PAGE |
| | AO-4 FOR STAIRS # 3 GOES THROUGH A |
| | PARKING SPACE. |
| | |
| | 9) A KNOX-BOX WILL BE REQUIRED FOR THE |
| | BUILDING. |
| | |
| | 10) SEVERAL DOOR SWINGS MAY BE |
| | IMPROPER ON THE ROOF PLAN DUE TO THE |
| | AMOUNT OF OCCUPANTS PROPOSED. |
| | |
| | 11) BATHROOMS ON ROOF APPEAR TO BLOCK |
| | EXIT ACCESS ON PAGE AO-10. |
| | |
| | 12) BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS. CERTAIN RESTRICTIONS WILL |
| | APPLY. PLEASE SEE APPENDIX F, LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 13) PLEASE INDICATE HOW ALL OF THE |
| | REQUIREMENTS OF FBC 412 IS BEING MET. |
| | |
| | 14) BUILDING ADDRESS REQUIRED ON |
| | PROPER ELEVATION. A MINIMUM OF 6" HIGH |
| | NUMBERS ARE REQUIRED. |
| | |
| | 15) CDX PLYWOOD IS BEING USED. AGAIN |
| | BE ADVISED THE BUILDING IS LOCATED |
| | IN THE FIRE LIMITS. CERTAIN |
| | RESTRICTIONS APPLY. |
| | |
| | 16) BUILDING WILL BE CONSIDERED A |
| | HIGH-RISE BUILDING FOR PURPOSES OF |
| | DETERMINING CODE COMPLIANCE. |
| | |
| | 17) PLEASE EXPLAIN PURPOSE OF COVERED |
| | TERRACE ON PAGE A5-4. |
| | |
| | 18) ELEVATOR WARNING SIGNS ARE REQUIRED |
| | AT ELEVATORS. |
| | |
| | 19) TACTILE SIGNAGE REQUIRED AT EXITS. |
| | |
| | 20) THE FIRE COMMAND ROOM ON PAGE |
| | M2.01 DOES NOT RELATE WITH OTHER |
| | PAGES ON THE DRAWINGS. |
| | |
| | 21) PLEASE DISPLAY ALL WINDOWS AND |
| | PANELS THAT ARE PLANNED TO MEET THE |
| | SMOKE CONTROL NOTE BOX LOCATED ON |
| | THE MECHANICAL PLANS. |
| | |
| | 22) THE WORDING "ANTICPATED STACK |
| | EFFECT" IS TO BE ADDED TO THE |
| | MECHANICAL SMOKE CONTROL PAGES. |
| | |
| | 23) THE GENERATOR EXHAUST SHALL BE |
| | LOCATED A MINIMUM OF 10 FEET FROM |
| | WALL OPENINGS OR MAKE UP AIR |
| | LOCATIONS. |
| | |
| | 24) THE FIRE COMMAND LOCATION ON |
| | ELECTRICAL DRAWINGS DO NOT RELATE TO |
| | OTHER DRAWINGS. |
| | |
| | 25) EXIT SIGN ARROWS POINTING WRONG |
| | DIRECTION ON PAGE E2.13. |
| | |
| | 26) ALL SMOKE DETECTORS SHALL BE |
| | INSTALLED A MINIMUM OF THREE FEET FROM |
| | AIR CONDITIONER DIFFUSERS. |
| | |
| | 27) THE FIRE COMMAND ROOM IN WRONG |
| | LOCATION ON PAGE FA2.01. |
| | |
| | 28) THE FIRE DEPARTMENT CONNECTION |
| | SHOWN ON PAGE C-10 DOES NOT RELATE |
| | TO OTHER DRAWINGS. |
| | |
| | 29) TAMPER SWITCHES, CHAIN AND LOCKS |
| | REQUIRED ON FIRE LINE BACKFLOW DEVICE. |
| | |
| | 30) ALL DEMOLITION, CONSTRUCTION, |
| | AND RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 31) PARKING GARAGE TO COMPLY WITH |
| | NFPA 88 A. |
| | |
| | 32) PLEASE PROVIDE A DETAILED DRAWING |
| | OF WHAT THE FIRE SMOKE CONTROL WILL |
| | LOOK LIKE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |