Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-01 00:00:001) SITE PLAN DOES NOT DISPLAY ANY
 EXISTING OR NEW FIRE HYDRANTS.
  
 2) EXIT STAIRS ARE REQUIRED TO BE
 KEPT UP WITH CONSTRUCTION.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 4) PLEASE EXPLAIN HOW ALL OF THE
 REQUIRED EQUIPMENT OF THE FBC, SECTION
 412 ARE EXPECTED TO FIT INTO THE
 SMALL COMMAND ROOM.
  
 5) HOW WILL EXIT DISCHARGE LOCATIONS
 BE MAINTAINED IN THE ALLEY. BY THE WAY
 WHO'S PROPERTY IS THE ALLEY.
  
 6) PLEASE INDICATE WHICH ELEVATORS
 WILL BE STRETCHER ACCESSIBLE.
  
 7) AN EXIT DISCHARGE LINE GOES
 THROUGH THE LOADING DOCK.
  
 8) THE TRAVEL DISTANCE LINE ON PAGE
 AO-4 FOR STAIRS # 3 GOES THROUGH A
 PARKING SPACE.
  
 9) A KNOX-BOX WILL BE REQUIRED FOR THE
 BUILDING.
  
 10) SEVERAL DOOR SWINGS MAY BE
 IMPROPER ON THE ROOF PLAN DUE TO THE
 AMOUNT OF OCCUPANTS PROPOSED.
  
 11) BATHROOMS ON ROOF APPEAR TO BLOCK
 EXIT ACCESS ON PAGE AO-10.
  
 12) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS WILL
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 13) PLEASE INDICATE HOW ALL OF THE
 REQUIREMENTS OF FBC 412 IS BEING MET.
  
 14) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6" HIGH
 NUMBERS ARE REQUIRED.
  
 15) CDX PLYWOOD IS BEING USED. AGAIN
 BE ADVISED THE BUILDING IS LOCATED
 IN THE FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY.
  
 16) BUILDING WILL BE CONSIDERED A
 HIGH-RISE BUILDING FOR PURPOSES OF
 DETERMINING CODE COMPLIANCE.
  
 17) PLEASE EXPLAIN PURPOSE OF COVERED
 TERRACE ON PAGE A5-4.
  
 18) ELEVATOR WARNING SIGNS ARE REQUIRED
 AT ELEVATORS.
  
 19) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 20) THE FIRE COMMAND ROOM ON PAGE
 M2.01 DOES NOT RELATE WITH OTHER
 PAGES ON THE DRAWINGS.
  
 21) PLEASE DISPLAY ALL WINDOWS AND
 PANELS THAT ARE PLANNED TO MEET THE
 SMOKE CONTROL NOTE BOX LOCATED ON
 THE MECHANICAL PLANS.
  
 22) THE WORDING "ANTICPATED STACK
 EFFECT" IS TO BE ADDED TO THE
 MECHANICAL SMOKE CONTROL PAGES.
  
 23) THE GENERATOR EXHAUST SHALL BE
 LOCATED A MINIMUM OF 10 FEET FROM
 WALL OPENINGS OR MAKE UP AIR
 LOCATIONS.
  
 24) THE FIRE COMMAND LOCATION ON
 ELECTRICAL DRAWINGS DO NOT RELATE TO
 OTHER DRAWINGS.
  
 25) EXIT SIGN ARROWS POINTING WRONG
 DIRECTION ON PAGE E2.13.
  
 26) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 27) THE FIRE COMMAND ROOM IN WRONG
 LOCATION ON PAGE FA2.01.
  
 28) THE FIRE DEPARTMENT CONNECTION
 SHOWN ON PAGE C-10 DOES NOT RELATE
 TO OTHER DRAWINGS.
  
 29) TAMPER SWITCHES, CHAIN AND LOCKS
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 30) ALL DEMOLITION, CONSTRUCTION,
 AND RENOVATION TO COMPLY WITH NFPA 241.
  
 31) PARKING GARAGE TO COMPLY WITH
 NFPA 88 A.
  
 32) PLEASE PROVIDE A DETAILED DRAWING
 OF WHAT THE FIRE SMOKE CONTROL WILL
 LOOK LIKE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL