Plan Review Notes
Plan Review Notes For Permit 04031591
Permit Number 04031591
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-26 00:00:00**************** UNSAT *************
  
 1)NOTE: PELASE SEE FIRE REVIEW COMMENTS
 AS WILL HAVE AN AFFECT ON SOME ELECTRI-
 -CAL PLANS.
 PLEASE ALSO SEE NOTES FROM ANY OTHER
 REVIEWERS AS THEY MAY ALSO HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE 61G15-23.002, PLEASE
 INCLUDE ALL REQ'D LICENSE #'S ON TITLE
 BLOCK AS REQ'D UNDER FS 471.023
 PLEASE ALSO HAVE ENGINEER SIGN PLANS
 WITH SIGNATURE AS SHOWN ON LICENSE/
 RAISED SEAL. INITIALS ARE NOT PERMITTED
 PER FS/ FBPE'S.
  
 3)NOTE: PLEASE SUBMIT MORE INFORMATION
 FOR LOCKED ROTOR OCP PER 695.4B1
 SIZED PERNEC LR.
  
 4)NOTE: PLEASE CLARIFY IF THERE IS ALSO
 GROUND LEVEL EGRESS TO OUTSIDE OF BLDG.
 IF SO, PLEASE PROIVDE LTNG PER 210.70
  
 5)NOTE: PLEASE PROVIDE NOTES FOR 700.8,
 700.9. PLEASE ALSO PROVIDE AIC RATING
 FOR GENERATOR MAX AVAILABLE FUALT
 CURRENT.
  
 6)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULES.
 PLEASE ARE NOT COMPLETE AT THIS TIME
 TO VERIFY THIS.
  
 7)NOTE: PLEASE NOTE GEN EXHAUST. THIS
 APPEARS TO HAVE A CONFLICT FOR EXHAUST
 10' OF OPENINGS/DOORS ETC.
  
 8)NOTE: LIGHTNING PROTECTION UNDER
 SEPARATE PERMIT.
 POOL ELECTRICAL WIRING ETC UNDER SEPARA-
 -TE PERMIT.
  
 9)NOTE:PLEASE SEE THAT THERE ARE AREAS
 IN GARAGE THAT SEEM TO HAVE LIGHTING
 MISSING.
  
 10)NOTE:PLEASE LABEL ALL PANELS ON PLANS
 SOME SHOWN WITH XX??
  
 11)NOTE: PLEASE SEE 210.52, RAILS AREAS
 ARE REQ'D TO HAVE OUTLETS.
  
 12)NOTE: PLEASE SEE SOME UNITS DO NOT
 SEEM TO BE COMPLETE WITH ELECTRICAL?
  
 13)NOTE: PLEASE PROVIDE NOTE FOR SHUTT-
 -ING DOWN OF GENERATOR/SIGNAGE REQ'D.
 230.2E
  
 14)NOTE:PLEASE SEE 250.6/ 250.24 THERE
 IS NO EQUIPMENT GROUNDING CONDUCTORS TO
 BE INSTALLED FROM FPL TO THE FIRST MEANS
 OF DISC.
  
 15)NOTE:: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%
 PER 230.42,215.2,215.3,210.19 ETC.
 SOME PANELS SHOW.
  
 16)NOTE: PLEASE PROVIDE NOTE FOR ALL
 REQ'D DOOR HARDWARE UNDER 2002 NEC
 110.26.
  
 17)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR WHIRLPOOL TUBS PER 680
  
 18)NOTE: PLEASE SEE NOTES PAGE:
 NOTE 1) MENTIONS ALL WIRING TO BE #12,
 YET PANEL SCHEDULES SHOW #14?
 PLEASE CORRELATE.
 NOTE 45)MENTIONS WINDS LOADS TO BE 110
 MPH. PLEASE SEE FBC FOR 140 MPH WIND
 LOAD.
 NOTE 56) SD'S TO BE A PART OF THE
 KIT/BATH LT CIRCUITS. PLEASE SEE 2002
 NEC 210.12. ARC FAULT PROTECTION FOR
 ALL OUTLETS.
  
 PLEASE NOTE: DUE TO PLANS NOT BEING
 COMEPLETE AT TIME OF PLAN REVIEW, THERE
 MAY BE OTHER COMMENTS ONCE PLANS HAVE
 BEEN COMPLETED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-04-23 00:00:001-ROLL OF PLANS IN ELECTRICAL FOR REVIEW
 PLAN REVIEW COMMENT S TO FOLLOW.
 ******* UNSAT ********
  
 PLANS SUBMITTED W/OUT BEING COMPLETE.
 PLAN REVIEW NOT COMPLETE AT THIS TIME.
 FURTHER REVIEW NOTES TO FOLLOW.
  
 DEWEY PALMER