| 2004-03-30 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) WORKING DRAWING REVIEW ONLY.NO |
| | PERMIT CAN BE ISSUED UNTIL THE PERMIT |
| | APPLICATION AND FEES ARE SUBMITTED. |
| | |
| | 2) THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 3) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 4) CONDOMINIUM V APARTMENTS.THE PLANS |
| | MAKE REFERENCE TO CONDOMINIUM.IF THE |
| | DWELLING UNITS ARE TO BE SOLD AS |
| | CONDOMINIUMS, NO CERTIFICATE OF |
| | OCCUPANCY CAN BE ISSUED UNTIL A |
| | 'DECLARATION OF CONDOMINIUM' HAS BEEN |
| | SUBMITTED TO THE STATE FOR APPROVAL, AND |
| | THEN RECORDED WITH THE CLERK OF THE |
| | COUNTY COURT.A RECORDED COPY SHALL BE |
| | SUBMITTED TO THE CITY FOR RECORDS, |
| | ADDRESSING PURPOSES, AND NOTIFICATION OF |
| | PALM BEACH COUNTY PROPERTY APPRAISER'S |
| | OFFICE. |
| | |
| | 5) FBC* 104.2.4SITE SURVEY.THE |
| | SUBMITTED SURVEY DRAWING HAS NOT BEEN |
| | SIGNED AND SEALED BY A LICENSED SURVEYOR |
| | AND MAPPER.THE SURVEY DRAWING DOES |
| | INCLUDE THE 'SURVEYORS CERTIFICATE', |
| | PRINTED NAME AND PRINTED LICENSE |
| | NUMBER OF BOTH PAUL J. STOWELL AND |
| | CLYDE MCNEAL.THE DRAWING SHALL BEEN |
| | SIGNED AND SEALED BY ONE OF THESE |
| | SURVEYORS. |
| | (REF: 472.025(1) FL. STATUTES) |
| | |
| | 6) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | NOTE: THE UNITY OF TITLE SHALL INCLUDE |
| | LOT 7, BLOCK 19, SOUTH OF THE ALLEY, |
| | WHICH IS SHOWN ON THE PLANS AS PART- |
| | APARTMENT UNIT AND PART-PARK AREA. |
| | |
| | 7) SUBMIT A RECORDED COPY OF THE AERIAL |
| | RIGHTS FOR CONSTRUCTION OVER THE RIGHT |
| | OF WAY.THE AERIAL RIGHTS SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE. |
| | |
| | 8) FBC* 105.13.1SPECIAL INSPECTOR.IT |
| | IS NOTED THAT THE STRUCTURAL INSPECTION |
| | PLAN IS PROVIDED ON SHEET S-0.SUBMIT |
| | A SIGNED THRESHOLD INSPECTOR AGREEMENT. |
| | FOR FURTHER DETAILS, CONTACT HAROLD |
| | PISKURA (THRESHOLD INSPECTION PROGRAM |
| | CO-ORDINATOR) ON 561-805 6711. |
| | |
| | 9) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.IT IS NOTED THAT SHEET S-0 REFERS |
| | TO ARDAMAN & ASSOCIATES REPORT 03-2186 |
| | (9/18/2003).SUBMIT THE GEOTECHNICAL |
| | REPORT. |
| | |
| | 10) FBC* 104.4.5 SPECIAL FOUNDATION |
| | PERMIT. THE BUILDING OFFICIAL MAY, AT |
| | HIS DISCRETION, ISSUE A SPECIAL PERMIT |
| | FOR THE FOUNDATION ONLY, UPON WRITTEN |
| | REQUEST BY THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH SPECIAL PERMIT IS PROCEED |
| | ING AT HIS/HER OWN RISK AND WITHOUT |
| | ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE |
| | REQUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODES. |
| | |
| | 11) A SEPARATE PERMIT APPLICATION WILL |
| | BE REQUIRED FOR THE SWIMMING POOL. |
| | |
| | 12) FBC 104.2.1.2SHEET A0-2, BUILDING |
| | DATA.THE BUILDING AREAS, ARRANGED BY |
| | STORY AND OCCUPANCY, SHALL BE STATED ON |
| | THE PLANS. |
| | |
| | 13) FBC TABLE 600SHEET A0-2, FIRE |
| | RESISTANCE RATINGS.THE PLANS SHALL |
| | STATE THE REQUIRED FIRE RESISTANCE |
| | RATINGS FOR THE WALLS, COLUMNS, BEAMS, |
| | FLOOR/CEILING ASSEMBLIES AND ROOF FOR A |
| | TYPE I BUILDING. |
| | |
| | 14) INFORMATIVE: |
| | FBC 104.2.1.2THE ARCHITECTURAL PLANS |
| | DO NOT INCLUDE A GENERAL NOTES/ |
| | SPECIFICATION SHEET. |
| | |
| | 15) FBC 705.1.1.2SHEET A-10.3, SOUTH |
| | ELEVATION OPENINGS.ALL OPENINGS IN |
| | WALLS LOCATED WITHIN 15 FEET OF THE |
| | PROPERTY LINE SHALL BE EQUIPPED WITH |
| | OPENING PROTECTIVES CONFORMING TO |
| | FBC 705.1.EXCEPTION (3) WILL NOT APPLY |
| | TO THE PARKING GARAGE LOUVERS BECAUSE IT |
| | IS NOT AN 'OPEN' PARKING STRUCTURE. |
| | |
| | 16) FBC 1001.1.3SHEET A0-4MEZZANINE |
| | PARKING LIFE SAFETY PLAN.ACCESS FROM |
| | THE PARKING GARAGE TO STAIR #3 AND |
| | ELEVATORS #3 AND #4 IS SHOWN THROUGH A |
| | PARKING SPACE WHICH HAS NOT BEEN |
| | 'PAINTED OUT'.AMEND THE PLAN TO SHOW |
| | AN UNOBSTRUCTED PATH BY 'PAINTING OUT' |
| | THE RELEVANT PARKING SPACE ON SHEETS |
| | A0-4 AND A1-3. |
| | |
| | 17) FBC 1004.1.4SHEET A0-5.THE TWO |
| | EXITS FROM THE PARKING GARAGE, AT THIS |
| | LEVEL, ARE SPACED APPROXIMATELY 80 FEET |
| | APART.THIS IS LESS THAN THE REQUIRED |
| | DISTANCE OF ONE-THIRD THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF |
| | THAT AREA, FOR A SPRINKLERED BUILDING. |
| | AMEND THE PLAN. |
| | |
| | 18) FBC 1012.1.2SHEET A0-6, THIRD |
| | FLOOR LIFE SAFETY PLAN.THE DOOR FROM |
| | THE LANDSCAPE COURT INTO THE SITTING |
| | AREA SHALL SWING IN THE DIRECTION OF |
| | EGRESS AS THE LANDSCAPE COURT AREA CAN |
| | ACCOMMODATE AN OCCUPANT LOAD IN EXCESS |
| | OF 50 PEOPLE.REVERSE THE SWING OF THE |
| | DOOR.SHOULD THIS DOOR BE MARKED #51 ON |
| | SHEET A1-6? |
| | |
| | 19) FBC 1012.1.2SHEET A0-7, FOURTH |
| | FLOOR LIFE SAFETY PLAN.THE DOOR FROM |
| | PAVED DECK AND LAWN AREAS INTO THE |
| | CORRIDOR SHALL SWING IN THE DIRECTION OF |
| | EGRESS AS THE DECK AND LAWN AREA CAN |
| | ACCOMMODATE AN OCCUPANT LOAD IN EXCESS |
| | OF 50 PEOPLE.REVERSE THE SWING OF THE |
| | DOOR.SHOULD THIS DOOR BE MARKED #74 ON |
| | SHEET A1-9? |
| | |
| | 20) FBC 1012.1.4SHEET A0-10, ROOF |
| | LEVEL LIFE SAFETY PLAN.THE RESTROOM |
| | DOOR SWING LEAVES LESS THAN HALF OF THE |
| | REQUIRED PASSAGEWAY WIDTH UNOBSTRUCTED. |
| | AMEND THE PLAN. |
| | |
| | 21) FBC 412.6SHEETS A0-3 TO A0-10, |
| | LIFE SAFETY PLANS.'FIRE PROTECTION |
| | COMPONENTS NOTE #13' IS NOT RELEVANT TO |
| | THIS PROJECT AND MAY CAUSE SOME |
| | CONFUSION. |
| | |
| | 22) FBC 11-4.8.5(2)SHEET A1-0, GROUND |
| | FLOOR PLAN.THE RAMP ADJACENT TO |
| | STAIR #1 SHALL BE AT LEAST 7'-11" LONG |
| | TO ACHIEVE THE REQUIRED LEVEL CHANGE |
| | WITH A SLOPE OF 1 IN 12. THE TOP LANDING |
| | IS SHOWN AT THE REQUIRED MINIMUM OF FIVE |
| | FEET FROM THE DOOR/WALL BUT THE RAMP IS |
| | DRAWN TOO SHORT.AMEND THE PLAN TO |
| | ENSURE THAT THERE WILL NOT BE A CONFLICT |
| | BETWEEN THE REQUIRED 18" MIN. RAMP |
| | HANDRAIL EXTENSION AND THE EXIT |
| | DISCHARGE FROM STAIR #1. |
| | |
| | 23) FBC 11-4.8.5(2)SHEET A1-0, GROUND |
| | FLOOR PLAN.EACH OF THE DWELLING UNITS |
| | (NOT THE MEZZANINE LEVEL OF THE TWO- |
| | STORY UNITS) IS REQUIRED TO COMPLY WITH |
| | FAIR HOUSING.DUE TO THE STAIRWAY SHOWN |
| | IN THE CORRIDOR BETWEEN LOFT 5 AND |
| | ELEVATOR #1, LOFTS 3, 5 AND 7 DO NOT |
| | HAVE ACCESS TO THE ELEVATORS, AND THE |
| | FACILITIES ON THE UPPER FLOORS, WITHOUT |
| | FIRST LEAVING THE BUILDING.AMEND THE |
| | CORRIDOR AND ELEVATOR LOBBY LEVELS AS |
| | NECESSARY TO ALLOW A RAMP, WITH FOUR |
| | FOOT TOP LANDING AND 18" HANDRAIL |
| | EXTENSION (AS REQUIRED BY FBC 11-4.8.5), |
| | INSTEAD OF STAIRS. |
| | |
| | 24) FBC 11-4.8.5SHEET A1-1, GROUND |
| | FLOOR PLAN.THE CORRIDOR RAMP BETWEEN |
| | GRIDS 15 AND 16 HAS A RISE OF MORE THAN |
| | 6", SO HANDRAILS ARE REQUIRED IN EACH |
| | SIDE.HANDRAILS ARE ALSO REQUIRED BOTH |
| | SIDES OF EACH OF THE GROUND FLOOR RAMPS |
| | THAT ARE LONGER THAN 72".AMEND THE |
| | PLANS. |
| | |
| | 25) FBC 11-4.8.5SHEET A1-1, GROUND |
| | FLOOR PLAN.THE RAMP BETWEEN LOFT-5 AND |
| | ELEVATOR #4 REQUIRES A FOUR FOOT LONG |
| | LANDING BETWEEN THE RAMP AND THE 'PUSH |
| | SIDE' OF THE ELEVATOR LOBBY DOOR. |
| | |
| | 26) FBC 412.6.2SHEETS A1-2 AND A1-3, |
| | MEZZANINE PLAN.THE A/C ROOMS SHALL NOT |
| | OPEN INTO THE ELEVATOR LOBBIES.AMEND |
| | THE PLANS. |
| | |
| | 27) FBC 1012.1.4SHEET A1-7, 3RD FLOOR |
| | PLAN.THE SWING OF DOOR #40 FROM THE |
| | PARKING GARAGE TO THE CORRIDOR, ADJACENT |
| | TO ELEVATOR #3, LEAVES LESS THAN HALF OF |
| | THE REQUIRED CORRIDOR WIDTH UNOBSTRUCTED |
| | AMEND THE PLANS TO RECESS THE DOORWAY. |
| | |
| | 28) FBC 1508ROOF COVERINGS. |
| | SHEETS A1-14 AND A1-15 DO NOT GIVE ANY |
| | DESCRIPTION OR SPECIFICATION FOR THE |
| | ROOF COVERINGS AT THIS LEVEL. |
| | |
| | 29) FBC 3003.4.1STRETCHER ACCESSIBLE |
| | ELEVATOR.IT IS NOTED THAT SHEET A7-2 |
| | SHOWS THE ELEVATOR SIZES AND SHEET A9-0 |
| | STATES THAT ELEVATOR #1 ACCOMMODATES AN |
| | AMBULANCE STRETCHER 76" LONG X 24" WIDE |
| | IN THE HORIZONTAL POSITION.THIS |
| | ELEVATOR SHALL BE IDENTIFIED BY SIGNAGE. |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 30) FBC 411.2.6SHEET A3-1, DOOR SCHED. |
| | 2ND FLOOR DOOR #40 SHALL BE 3/4-HOUR |
| | FIRE-RATED.AMEND THE PLAN. |
| | |
| | 31) FBC 704.2.4SHEET A1-6, 3RD FLOOR |
| | SITTING AREA.THIS ROOM SHALL BE |
| | SEPARATED FROM THE EXIT ACCESS CORRIDOR |
| | BY 1/2-HOUR FIRE-RATED WALLS AND A |
| | 20 MINUTE FIRE-RATED DOOR.THE DOOR |
| | SHALL SWING IN THE DIRECTION OF EGRESS |
| | BUT ITS SWING SHALL NOT OBSTRUCT MORE |
| | THAN HALF OF THE REQUIRED CORRIDOR |
| | WIDTH. |
| | |
| | 32) FBC 704.2.4SHEETS A1-6 TO A1-13, |
| | 3RD FLOOR TO 8TH FLOOR PLANS.WHAT |
| | APPEARS TO BE A MECHANICAL ROOM (NOT |
| | LABELLED) AT THE CORRIDOR INTERSECTION |
| | OPPOSITE THE ELECTRICAL AND TENANT |
| | STORAGE ROOMS DOES NOT HAVE A DOOR |
| | REFERENCE.NO APPROPRIATE REFERENCE CAN |
| | BE FOUND ON THE DOOR SCHEDULE |
| | (SHEET A3-1).A MINIMUM OF 20 MINUTE |
| | FIRE-RATED DOOR IS REQUIRED AT THESE |
| | LOCATIONS.AMEND THE PLANS/SCHEDULE. |
| | |
| | 33) FBC 705.1.2SHEETS A0-3 TO A0-9 DO |
| | NOT SPECIFY THE REQUIRED TWO-HOUR FIRE- |
| | RATING FOR THE SHAFTS, INCLUDING THOSE |
| | ADJACENT TO ELEVATOR #1 AND ELEVATOR #4 |
| | AND THOSE WITHIN THE MECHANICAL ROOM |
| | REFERENCED IN COMMENT #32 ABOVE.AMEND |
| | THE PLANS. |
| | |
| | 34) FBC 411.2.6, 705.2.4 AND 1005.6.2 |
| | SHEET A3-1, DOOR SCHEDULE, SHOWS DOOR |
| | #36 TO #74 AS REFERENCES FOR DOORS ON |
| | 2ND TO 4TH FLOORS, BUT SHEETS A1-4 TO |
| | A1-9 (2ND TO 4TH FLOOR PLANS) SHOW DOORS |
| | AS #80 TO #86.AMEND THE PLANS SO THAT |
| | THE REQUIRED FIRE-RATING OF THE DOORS |
| | CAN BE DETERMINED/VERIFIED. |
| | |
| | 35) FBC* F102.2.7SHEETS A4-2 AND A1-6, |
| | TRELLIS STRUCTURE.ARCHITECTURAL TRIM, |
| | ON BUILDINGS LOCATED IN THE FIRE |
| | DISTRICT, SHALL BE CONSTRUCTED OF |
| | APPROVED NON-COMBUSTIBLE MATERIALS OR |
| | FIRE RETARDANT TREATED WOOD.ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 36) FBC* F102.2.8SHEETS A4-0 TO A4-3 & |
| | SHEETS A5-0 TO A5-2. PERMANENT CANOPIES/ |
| | AWNINGS AND THEIR SUPPORTS, ON BUILDINGS |
| | LOCATED IN THE FIRE DISTRICT, SHALL BE |
| | OF NON-COMBUSTIBLE MATERIAL, FIRE |
| | RETARDANT TREATED WOOD, WOOD OF TYPE III |
| | SIZES OR OF 1-HOUR RESISTANT |
| | CONSTRUCTION.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 37) FBC 1608.2.2GUARDRAIL STRENGTH. IT |
| | IS NOTED THAT SHTS A7-0,A7-1,A7-6 & A8-3 |
| | STATE THE HANDRAIL STRENGTH REQIREMENTS. |
| | ALSO, THE GUARDRAILS SHALL BE DESIGNED |
| | AND CONSTRUCTED FOR A CONCENTRATED LOAD |
| | OF 200 LB APPLIED IN ANY DIRECTION AT |
| | THE TOP OF THE GUARDRAIL, A CONCENTRATED |
| | HORIZONTAL LOAD OF 200 LB APPLIED ON A |
| | 1 SQ FT AREA AT ANY POINT, AND A LINE |
| | LOAD OF 50 PLF APPLIED HORIZONTALLY AT |
| | THE REQUIRED GUARDRAIL HEIGHT WITH A |
| | SIMULTANEOUS LINE LOAD OF 100 PLF |
| | APPLIED VERTICALLY DOWNWARD ON THE TOP |
| | OF THE GUARDRAIL.THESE LOADS SHALL NOT |
| | BE APPLIED SIMULTANEOUSLY (UNLESS NOTED |
| | ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY |
| | TO PRODUCE MAXIMUM STRESS IN EACH OF THE |
| | COMPONENTS OR SUPPORTS.AMEND/ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 38) FBC 1606.1.7WIND LOAD. IT IS NOTED |
| | THAT SHEET S-0 STATES BASIC WIND SPEED, |
| | WIND IMPORTANCE FACTOR AND WIND EXPOSURE |
| | CATEGORY.THE PLAN SHALL ALSO STATE THE |
| | INTERNAL PRESSURE COEFFICIENT (0.18) AND |
| | THE COMPONENT AND CLADDING DESIGN WIND |
| | PRESSURES INCL ROOF.AMEND THE PLANS. |
| | ALSO, SUBMIT THE REFERENCE RWDI WIND |
| | TUNNEL TEST REPORT. |
| | |
| | 39) SHEETS S-33 AND S-34POOL DECK AND |
| | ROOF REINFORCING PLANS.THESE PLANS ARE |
| | NOT COMPLETE. |
| | |
| | 40) FBC 903.7.6SHEETS FP2.03 & FP2.04, |
| | MEZZANINE SPRINKLER PLANS DO NOT SHOW |
| | SPRINKLER COVERAGE IN EITHER OF THE |
| | ELEVATOR LOBBIES. |
| | |
| | 41) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 42) FBC 1005.6.9.9SHEET M6.01, STAIR |
| | PRESSURIZATION RISER.THE NOTE BELOW |
| | EACH (#1, #2 AND #3) STAIR RISER DIAGRAM |
| | SPECIFIES A MINIMUM PRESSURE |
| | DIFFERENTIAL OF 0.5" W.G.THIS SHOULD |
| | READ 0.05" W.G. AS IT EXCEEDS THE |
| | MAXIMUM ALLOWABLE POSITIVE PRESSURE. |
| | AMEND THE NOTE. |
| | |
| | 43) SUBMIT PRODUCT APPROVALS FOR THE |
| | WINDOWS, STOREFRONT, EXTERIOR DOORS, |
| | SLIDING GLASS DOORS AND ROOF COVERINGS. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 44) PRODUCT APPROVAL.RULE 9B-72 FAC. |
| | FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE |
| | PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL |
| | CAN BE ACHIEVED IF THERE IS A QUALITY |
| | ASSURANCE PROGRAM IN PLACE WITH A STATE |
| | APPROVED QUALITY ASSURANCE ENTITY.IF |
| | NEITHER IS APPLICABLE, THEN SITE |
| | SPECIFIC APPROVAL IS REQUIRED.LOCAL |
| | PRODUCT APPROVAL WILL ALLOW A PRODUCT TO |
| | BE USED, IN ACCORDANCE WITH THE TEST |
| | CRITERIA, THROUGHOUT THE JURISDICTION OF |
| | WEST PALM BEACH.SITE SPECIFIC PRODUCT |
| | APPROVAL WILL ALLOW A PRODUCT TO BE |
| | USED ONLY ON THE PROJECT FOR WHICH THAT |
| | SITE SPECIFIC APPROVAL IS GRANTED. |
| | LOCAL AND SITE SPECIFIC PRODUCT APPROVAL |
| | APPLICATION FORMS ARE AVAILABLE FROM |
| | THIS OFFICE.APPROVED QUALITY ASSURANCE |
| | ENTITIES ARE LISTED ON THE DCA WEBSITE: |
| | WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_ |
| | REGI_SRCH.ASP |
| | |
| | 45) SHEET A3-2. IT IS NOTED THAT THE |
| | SLIDING GLASS DOOR AND SINGLE HUNG |
| | WINDOW DETAILS SPECIFY FRAME ATTACHMENT. |
| | NOTE THAT THE FRAME ATTACHMENT SHALL BE |
| | AS PER THE RELEVANT PRODUCT APPROVAL, OR |
| | BETTER. |
| | |
| | 46) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |