| 2004-05-08 00:00:00 | ******* REVISION/ PROVISO ********* | | | | | | 1)NOTE: PLANS NOW HAVE BEEN RESUBMITTED | | | SHOWINGPANELS AS MCB, HOWEVER PANEL | | | SCHEDULES SHOW PANELS MLO? | | | PLANS ALSO NOW INDICATE A POOL PANEL, | | | WHICH WAS NOT ON ORIG PLANS AND IS NOT | | | ON RISER DIAGRAM. | | | | | | 2 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLANS TO BE REVISED AND SUBMITTED FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|