Plan Review Notes
Plan Review Notes For Permit 04031573
Permit Number 04031573
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-08 00:00:00******* REVISION/ PROVISO *********
  
 1)NOTE: PLANS NOW HAVE BEEN RESUBMITTED
 SHOWINGPANELS AS MCB, HOWEVER PANEL
 SCHEDULES SHOW PANELS MLO?
 PLANS ALSO NOW INDICATE A POOL PANEL,
 WHICH WAS NOT ON ORIG PLANS AND IS NOT
 ON RISER DIAGRAM.
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLANS TO BE REVISED AND SUBMITTED FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717