| Plan Review Notes For Permit 04031569 |
| Permit Number |
04031569 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-08 00:00:00 | ********* REVISION/ PROVISO ******** | | | | | | 1)NOTE: PLEASE CORRELATE PANELS/SCHEDULE | | | S AND RISER DIAGRAM. POOL PANEL IS STILL | | | MISSING FROM RISER.?? | | | PANELS ON PANEL SCHEDULES ARE STILL | | | SHOWN AS MLO?, YET RISER SHOWS MCB. | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT IN | | | BEDRM #4. 210.52 2' OF WALL. | | | | | | 3)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE REVISE PLANS FOR ABOVE COMMENTS | | | BEFORE ROUGH ELECTRICAL INSPECTION. | | | SUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|