2004-05-08 00:00:00********* REVISION/ PROVISO ********
  
 1)NOTE: PLEASE CORRELATE PANELS/SCHEDULE
 S AND RISER DIAGRAM. POOL PANEL IS STILL
 MISSING FROM RISER.??
 PANELS ON PANEL SCHEDULES ARE STILL
 SHOWN AS MLO?, YET RISER SHOWS MCB.
  
 2)NOTE: PLEASE SEE MISSING RECEPT IN
 BEDRM #4. 210.52 2' OF WALL.
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE REVISE PLANS FOR ABOVE COMMENTS
 BEFORE ROUGH ELECTRICAL INSPECTION.
 SUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717