| 2004-04-06 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | PLEASE SUBMIT PLANS,ELECTRICAL CALCULAT- | | | IONS FOR THE INTENDED SCOPE OF WORK PER | | | 104.1.3, 104.2.1 FLORIDA BUILDING CODE, | | | 2001 AND 215.5 NEC 2002. THIS WORK MUST | | | BE PERMITTED TO, AND INSTALLED BY AN ELE | | | CTRICAL CONTRACTOR PURSUANT TO CHAPTER | | | 489 FLORIDA STATUTES. | | | | | | A RISER DIAGRAM IS REQUIRED FOR THE NEW | | | SERVICE. | | | | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|