2004-04-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031543
 ADD: 1555 PALM BEACH LAKES BLVD
 CONT: WINFREE
 TEL: (561)262-2687
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) DOOR SCHEDULE, CORRECT "C" LABEL
 DOORS, TABLE 705.1.2 INDICATES BUILDINGS
 WITH FIRESPRINKLER, EXIT ACCESS COORI-
 DORS REQUIRE 20 MINUTE RATING.
  
 3) HIGH RISE, ELEVATOR LOBBIES, 412.6.2
 ELEVATOR LOBBIES REQUIRE FIRE RATED DOOR
 SEPERATING IT FROM OTHER ROOMS.
 PLAN MAY HAVE DOORS SINCE THE ELEC,MECH
 PLANS INDICATE EXISTING DOORS, BUT THE
 ELECTRIC, LIGHTING & MECHANICAL PLANS
 DO INDICATE THEY ARE FOR THE "SIXTH
 FLOOR NOT THE FIFTH"?CORRET.
  