| 2004-04-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 2) POOL PIPING SCHEMATIC SHOWS 2 SETS OF |
| | POOL MAIN DRAINS AND TWO SKIMMER LINES, |
| | BUT ONLY ONE OF EACH ON THE POOL LAYOUT |
| | PLAN. PLEASE CLAIRFY. ALSO SHOW HOW THE |
| | VACUUM CLEANING LINE CONNECTS TO THE |
| | SUCTION PIPING. SCHEMATIC SHALL REFLECT |
| | THE INSTALLATION, AND THE POOL LAYOUT. |
| | 3) SECOND SHEET ABOVE TYPICAL WALL SECT- |
| | ION & WELL POINT DETAIL WORDING IS NOT |
| | CLEAR AND UNREADABLE. PLANS SHALL HAVE |
| | SUFFICIENT CLARITY AND DETAIL PER SECT- |
| | ION 104.2.1 |
| | 4 ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |