Plan Review Notes
Plan Review Notes For Permit 04031454
Permit Number 04031454
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2) POOL PIPING SCHEMATIC SHOWS 2 SETS OF
 POOL MAIN DRAINS AND TWO SKIMMER LINES,
 BUT ONLY ONE OF EACH ON THE POOL LAYOUT
 PLAN. PLEASE CLAIRFY. ALSO SHOW HOW THE
 VACUUM CLEANING LINE CONNECTS TO THE
 SUCTION PIPING. SCHEMATIC SHALL REFLECT
 THE INSTALLATION, AND THE POOL LAYOUT.
 3) SECOND SHEET ABOVE TYPICAL WALL SECT-
 ION & WELL POINT DETAIL WORDING IS NOT
 CLEAR AND UNREADABLE. PLANS SHALL HAVE
 SUFFICIENT CLARITY AND DETAIL PER SECT-
 ION 104.2.1
 4 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]