2004-04-23 00:00:00********* NOTES REDLINED ********
  
  
 CABINETS ARE NOT PERMITTED TO GO BACK
 INFRONT AND AROUND PANEL IN VIOLATION
 OF 110.26
 SPOKE TO CHIEF ELECTRICAL INSPECTOR,
 AND UNDERSTOOD ONLY COUNTERTOPS WERE
 BEING REPLACED, WHEN EXPLAINED KITCHEN
 HAD DEMO PERMIT AND ALL CABINETS ETC
 ARE NEW, 110.26 STANDS.
 PLANS SHOW CREATING YOUR OWN VIOLATION
 AND PLANS ARE CLEARLY REDLINED THAT
 PANEL MUST MEET 110.26!!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW