| Plan Review Notes For Permit 04031325 |
| Permit Number |
04031325 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-13 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLANS SHOW ELECTRICAL PANEL | | | AS EXISTING IN KITCHEN AND NEW CABINETS | | | ETC BEING INSTALLED INFRONT. THIS WILL | | | NOT BE PERMITTED UNDER 110.26 NEC. | | | MUST MEET CLEARENCE REQ'MENTS. | | | PLEASE VERIFY AND/OR MOVE LOCATION OF | | | PANEL. | | | | | | 2)NOTE: PLEASE PROVIDE SIZE AND LOAD | | | ON PANEL WITH NEW CIRCUITS BEING ADDED. | | | 215.5/220 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|