| Plan Review Notes For Permit 04031325 |
| Permit Number |
04031325 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04031325 | | | ADD: 2800 N FLAGLER/ 406 | | | CONT: NDS CONSTRUCTION | | | TEL: (561)236-5187 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: APPROVED/ PROVISO | | | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 3) TYPE I OR II BUILDING, 609.2.1 | | | PARTITIONS AND BACKING SHALL BE NON | | | COMBUSTIBLE OR FIRE RETARDANT TREATED | | | WOOD. |
|