| Plan Review Notes For Permit 04031265 |
| Permit Number |
04031265 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-26 00:00:00 | 1) PLANS DO NOT INDICATE IF THE | | | BUILDING IS FIRE SPRINKLER PROTECTED. | | | IT IS BELIEVED THAT IT IS. PLEASE | | | ANNOTATE PLANS WITH PROPER | | | INFORMATION. | | | | | | 2) NO COMBUSTIBLES ARE ALLOWED IN A | | | RETURN AIR PLENUM. | | | | | | 3) PLEASE SHOW ALL EXISTING OR NEW | | | FIRE EXTINGUISHERS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|