| Plan Review Notes For Permit 04031253 |
| Permit Number |
04031253 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-07-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FBC-2001 FUEL GAS | | | | | | 1) BY REMOVING THE KITCHEN DRAWINGS, THE | | | SHEETS WITH THE DBPR PLAN REVIEW STAMP, | | | REQUIRED FOR PLAN REVIEW HAVE BEEN RE- | | | MOVED. | | | 2) FROM PREVIOUS REVIEWS: TOTAL BTU'S ON | | | GAS SYSTEM AND TOTAL DEVELOPED LENGTH | | | (MOST REMOTE FROM METER) SHALL BE PRO- | | | VIDED TO REVIEW GAS PLANS. SUBMIT A GAS | | | RISER ISOMETRIC SHOWING EXISTING PIPING | | | WITH PIPE SIZE, INDICATE THE DISTANCE TO | | | THE MOST REMOTE OUTLET FROM THE METER IN | | | THE SYSTEM. | | | 3) MANUF. SHEETS FOR THE GAS APPLIANCES | | | WERE NOT SUBMITTED AND ARE REQUIRED FOR | | | GAS REVIEW. THESE WHERE SUBMITTED EARL- | | | IER BUT WERE NOT RESUBMITTED AT THIS | | | TIME. | | | 4) I WILL TRY TO CONTACT R. COMPO CON- | | | CERNING THE GREASE INTERCEPTORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|