| Plan Review Notes For Permit 04031253 |
| Permit Number |
04031253 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-14 00:00:00 | PERMIT TO BE APPLIED FOR SEPARATELY, | | | PLANS TO BE SUBMITTED WITH PERMIT | | | APPLICATION. | | | 1.PLAN SHEET MP303 INDICATES DUCT WORK | | | FOR HOOD #1.PLEASE PROVIDE DUCT LAYOUT | | | FOR HOOD #2. | | | | | | 2.PLEASE INDICATE ELEVATION OF GREASE | | | DUCT.PLAN SHEET MP303 & K-4 STATE THE | | | FANS ARE ON THE ROOF.PROVIDE DETAIL | | | OF CLEARANCE TO COMBUSTIBLES OR THE | | | CLEARANCE REDUCTION METHOD THAT WILL | | | BE USED (I.E. SHAFT, FIRE WRAP, FLAMEBAR | | | DUCT?). | | | | | | 3.SEPARATE PERMIT REQUIRED FOR THE | | | HOOD & FIRE SUPPRESSION.CONTRACTOR IS | | | NOT SIGNED ON WITH BUILDING PERMIT. | | | | | | 4.PROVIDE INSTALLATION DETAIL FOR THE | | | ROOF MOUNTED FANS. PLANS NOTE A 10 FT | | | SEPARATION BETWEEN EXHAUST & FRESH AIR | | | INTAKES. | | | | | | 5.EXHAUST FANS ARE TO BE A MINIMUM OF | | | 40" ABOVE THE THE ROOF SURFACE PER NFPA | | | 96. | | | | | | 6.AIR VELOCITY THROUGH THE GREASE DUCT | | | SYSTEMS SHALL BE NOT LESS THAN 1,500 FPM | | | & NOT GREATER THAN 2,500 FPM. 2001 FBC/M | | | 506.3.6 | | | | | | 7.PLEASE PROVIDE DETAIL FOR THE ANSUL | | | SYSTEM FOR HOOD #2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|