| Plan Review Notes For Permit 04031252 |
| Permit Number |
04031252 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-05 00:00:00 | DENIED: | | | 1.PLAN SHEET 3 OF 3 A/C PLAN, DUCT | | | SIZE TO ONE OF THE SUPPLY TO BEDROOM IS | | | NOT SIZED (1-10" & 1-4" TO THE BATHROOM) | | | IT APPEARS THE OTHER SUPPLY DUCT WOULD | | | BE A 10" ALSO.PLEASE CLARIFY. | | | | | | 2.RETURN AIR REQUIRED TO THE BEDROOM | | | AREA FOR COMPLIANCE WITH 2001 FBC(M) | | | 601.4.PLEASE SEE THE ATTACHED SCHEDULE | | | FOR PROPER SIZING. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|