| 2004-04-02 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE PANEL SCHEDULE NOTES INDICATE A |
| | 200 AMP SERVICE. THE RISER IS LABLED |
| | 150 AMP. PLEASE CORRELATE. |
| | |
| | 2} PER 220.31 THERE IS NO DEMAND TAKEN |
| | FOR THE A/C. ALSO NOTE THAT THIS LOAD |
| | CALCULATION ALLOWS ALL BUT THE 1ST |
| | 8000VA TO BE TAKEN @ 40%. RECALCULATE |
| | LOAD AND INDICATE METHOD USED. (ARTICLE |
| | #.) |
| | |
| | 3} THE LOADS FOR THE HEAT STRIP & COND. |
| | UNIT ARE REVERSED ON THE SCHEDULE. |
| | |
| | 4} RECEPTACLES NEED TO BE ADDED IN THE |
| | BEDROOM TO COMPLY WITH 210.52(A). |
| | |
| | 5} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | THAT BRANCH CIRCUIT CODE COMPLIANCE CAN |
| | BE DETERMINED. |
| | |
| | 6} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 7} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 8} ISLAND RECEPTACLES MUST BE GFI |
| | PER210.8(A)(6). |
| | |
| | 9} A RECEPTACLE MUST BE ADDED AT THE |
| | BACK OF THE HOUSE (OUTSIDE PER |
| | 210.52(E). |
| | |
| | 10} SEE PLUMBING COMMENTS FOR TITLE |
| | BLOCK & SEAL REQUIREMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL, |
| | ALSO NOTE CODE REDLINED SET OF PLANS. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |