Plan Review Notes
Plan Review Notes For Permit 04031143
Permit Number 04031143
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-23 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SHOW NEW HEAT PUMP ON
 WIRING DIAGRAM. THIS IS NOT SHOWN.
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATION
 FOR EXISITNG SERVICE AND INCLUDE ALL
 NEW LOADS. PLEASE ALSO INDICATE SIZE
 OF EXSITING SERVICE..
  
 THESE ARE NEW COMMENTS AND SHOULD HAVE
 BEEN REQUESTED ON ORIG REVIEW. IF PLANS
 COME BACK WITH THESE AS THE ONLY COMMENT
 -S, A RESUB FEE WILL NOT BE DUE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  