| Permit Number |
04031143 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-04-23 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW NEW HEAT PUMP ON | | | WIRING DIAGRAM. THIS IS NOT SHOWN. | | | | | | 2)NOTE: PLEASE PROVIDE LOAD CALCULATION | | | FOR EXISITNG SERVICE AND INCLUDE ALL | | | NEW LOADS. PLEASE ALSO INDICATE SIZE | | | OF EXSITING SERVICE.. | | | | | | THESE ARE NEW COMMENTS AND SHOULD HAVE | | | BEEN REQUESTED ON ORIG REVIEW. IF PLANS | | | COME BACK WITH THESE AS THE ONLY COMMENT | | | -S, A RESUB FEE WILL NOT BE DUE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|