Plan Review Notes
Plan Review Notes For Permit 04031091
Permit Number 04031091
Review Stop P
Sequence Number 2
Notes
Date Text
2004-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESS. COMMENT NUMBER SHALL
 REMAIN THE SAME TO AVOID CONFUSION.
 3) SHT A-3 SPECIFICATION WORK SHEETS RE-
 FERED TO BY DBPR STAMP (3) SHALL BE SUB-
 MITTED. 1 COPY WITH EACH SET OF PLANS.
 SECTION 104.2.1.
 5) SHT A-3 S-13 GREASE INTECEPTOR NOT
 APPROVED UNDER SINK.(ALSO SEE SHEET P-3)
 ALSO PER RODNEY COMPO A SAMPLE POINT IS
 REQUIRED ON SANITARY BLDG DRAIN PRIOR TO
 DRAINING INTO TOILET ROOMS. (SEE ATTACH-
 ED SHEET). SHOW LOCATION OF SAMPLE POINT
 ON RISER DIAGRAM AND ON FLOOR PLAN.
 WASTE ORD. #2938-96.
 7) SHT P-3 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. PDI-WH 201/SECTION 604.9
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 *******NOTE: NO NOT REMOVE SHT A3 OF 8
 AS THIS SHEET HAS THE DBPR STAMP********
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]