Plan Review Notes
Plan Review Notes For Permit 04031091
Permit Number 04031091
Review Stop P
Sequence Number 1
Notes
Date Text
2004-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED.
 2) SHT A-2 ALL CAPPED AND DEMO'ED PLUMB-
 ING LINES SHALL BE INSPECTED PRIOR TO
 COVERING.
 3) SHT A-3 SPECIFICATION WORK SHEETS RE-
 FERED TO BY DBPR STAMP (3) SHALL BE SUB-
 MITTED. 1 COPY WITH EACH SET OF PLANS.
 SECTION 104.2.1
 4) SHTS A-3 & P-1 FIXTURE SCHEDULE, X5A
 SHOWS QUANTITY 2, NONE FOUND. PLEASE
 CLAIRFY. SECTION 104.2.1
 5) SHT A-3 S-13 GREASE INTECEPTOR NOT
 APPROVED UNDER SINK. CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE, WASTE
 ORD. 2938-96 @ (561) 837-4074 FOR GREASE
 INTECEPTOR REQUIREMENTS.
 6) SHT P-2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECT-
 ION 604.9
 7) SHT P-3 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. PDI-WH 201/SECTION 604.9
 8) AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THIS SPACE. INSTALLED
 A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 SERVICING AND CERTIFICATION. SECTION
 608.13.2
 9) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER SECTION
 607.3.2
 10) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT ACCEPTABLE
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 THE SEAL SHALL BE PRESSED SO THAT IT CAN
 BE READ. UNABLE TO READ NAME OF ENGINEER
 AND TYPE OF PROFESSIONAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]