2004-04-10 00:00:00PROVISO:
 ROOF CURB SHALL BE A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE PER 2001 FBC
 1511.7.
  
 PLEASE PROVIDE INFORMATION ON THE
 CONDENSATE; LINE SIZE, PIPE MATIERIAL
 AND TERMINATION.PER CITY CODE SECTION
 90-125 (5), CONDENSATE SHALL TERMINATE
 TO STORM DRAIN NOT THE SANITARY. PLEASE
 CLARIFY.
  
 SEPARATE PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZERS AND COOLERS WITH REMOTE
 CONDENSERS.PROVIDE MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.