| 2004-04-14 00:00:00 | *************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | ALL INFORMATION REQ'D ON TITLE BLOCK FOR |
| | ENGINEER AND ENGINEERING FIRM. |
| | PLEASE INCLUDE NAME(S) AND ALL LICENSE |
| | #'S AS REQ'D INCLUDING CA#. |
| | PLEASE BE SURE RAISED SEALED IS CLEAR |
| | AND VISABLE.PLEASE SEE PLUMB REVIEW FOR |
| | THIS COMMENTALSO. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE "B" |
| | INDICATES SHOW WINDOW AND SIGN CIRCUIT |
| | AS SEPARATE YET, PLANS INDICATE BOTH ON |
| | CIRCUIT B-9? PLEASE CORRELATE. |
| | |
| | 3)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS MAY BE REQ'D BY |
| | OTHER TRADES TO VERIFY PREVIOUS. |
| | PLEASE SEE OTHER REVIEWERS NOTES. |
| | |
| | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 5)NOTE: PLEAS VERIFY LOCATION OF NEW |
| | MAIN DISC? PLEASE ALSO VERIFY WHERE |
| | NEW MAIN IS BEING FED FROM? SAME FPL |
| | TRANSFORMER? 230.72, 230.2 |
| | |
| | 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | -S AT 125%(LIGHTING ETC)(LARGEST MOTORS) |
| | 215.2,215.3,230.42 ETC |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |