| 2004-04-09 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04031091 |
| | ADD: 801 VILLAGE BLVD# 307 |
| | CONT: RCC ASSOCIATES |
| | TEL: (954)325-7273 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FIXED STOREFRONT WINDOWS |
| | B) STOREFRONT SWING DOORS |
| | C) STORM SHUTTERS IF GLAZING NOT TESTED |
| | FOR LARGE MISSLE IMPACT. |
| | |
| | 3)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 4) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 5) CHANGES IN LEVEL 11-4.5.2 CHANGES IN |
| | LEVEL UP TO 1/4 IN. MAY BE VERTICAL AND |
| | WITHOUT EDGE TREATMENT. CHANGES IN LEVEL |
| | BETWEEN 1/4IN AND 1/2IN SHALL BE BEVELED |
| | WITH A SLOPE NO GREATER THAN 1:2. |
| | CHANGES GREATER THAN 1/2IN SHALL BE |
| | ACCOMPLISHED BY MEANS OF A RAMP THAT |
| | COMPLIES WITH 11-4.7 OR 11-4.8. |
| | |