| 2004-05-04 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)DAVID LAWRENCE ARCHITECTURE INC. |
| | IS REQUIRED TO HAVE A CERTIFICATE OF |
| | AUTHORIZATION.PROVIDE THE NUMBER |
| | (SHEET 1).IF YOU REMOVE THE NAME, |
| | MASTERS CANNOT BE REDLINED (CLEAN |
| | ORIGINALS REQUIRED), EACH SHEET. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM #4.THE |
| | PRODUCT APPROVALS SUBMITTED FOR DOUBLE |
| | DOORS ARE INSWING OR IMPACT.ARE YOU |
| | USING IMPACT FOR THE REAR DOUBLE DOOR |
| | AS WELL AS THE FRONT? |
| | |
| | 3.)WHERE IS THE KEY PLAN FOR THE |
| | HURRICANE INSTALLATION SCHEDULE?IS |
| | THE DOOR REQUIRED TO BE IMPACT STILL ON |
| | THIS SCHEDULE? |
| | |
| | 4.)FLORIDA STATEWIDE, LOCAL OR SITE |
| | SPECIFIC PRODUCT APPROVAL REQUIRED FOR |
| | ALL WINDOWS AND DOORS.PLEASE PROVIDE |
| | FOR THE ODL IMPACT DOOR. |
| | |
| | 5.)THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE SINGLE IMPACT GLASS DOOR IS LIMITED |
| | TO 3'0, DOOR ON THE PLAN IS 3'3". |
| | |
| | 6.)THE NON IMPACT DOOR PRODUCT |
| | APPROVAL SUBMITTED IS ALSO LIMITED IN |
| | SIZE TO 3'0.THE 2ND FLOOR DOOR IS 3'3. |
| | |
| | 7.)THE SIMONTON WINDOW PRODUCT |
| | APPROVALS ARE ILLEGIBLE AND REQUIRE |
| | FL STATE, LOCAL OR SITE SPECIFIC |
| | PRODUCT APPROVAL.ONE SHEET WAS FOR |
| | A FIXED WINDOW, NO WINDOWS OF THAT |
| | TYPE ON THE PLAN.THE OTHER WAS FOR |
| | A SINGLE HUNG; THERE IS ALREADY AN |
| | APPROVED SINGLE HUNG WINDOW IN THE |
| | PACKAGE (TRACO).IS THIS AN ALTERNATE? |
| | |
| | 8.)PROVIDE WINDOW MULLION PRODUCT |
| | APPROVALS.FL STATE, LOCAL OR SITE |
| | SPECIFIC REQUIRED IN ADDITION TO THE |
| | TEST REPORT. |
| | |
| | 9.)THE TRUSS SHEETS SUBMITTED ARE |
| | LOOSE.COLLATE, SUBMIT TWO IDENTICAL |
| | BOUND (STAPLED) COPIES.SOME SHEETS |
| | ARE LACKING A TITLE BLOCK.A FULL |
| | SIGNATURE IS REQUIRED, NOT INITIALS PER |
| | FBPE AND BUILDING OFFICIAL.BCLL IS |
| | SHOWN AS 0; REVISE TO BE CONSISTENT WITH |
| | THE PLANS AND FBC TABLE 1604.1. |
| | |
| | 10.) ADDITIONAL FEES DUE $190, SEE |
| | ATTACHED BZ238899.THIS IS A MAJOR |
| | WORKING DRAWING REVIEW, NOT A PERMIT |
| | APPLICATION WITH RESUBS. |