| Plan Review Notes For Permit 04031090 |
| Permit Number |
04031090 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-25 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE CONDUCTOR SIZE FOR THE SERVICE ON | | | THE RISER DIAGRAM IS UNDERSIZED PER | | | 210.15(B)(6). MUST BE MINIMUM #2/0. | | | | | | 2} PLEASE SEE 250.50 FOR GROUNDING AND | | | AMMEND NOTE #4 ON RISER NOTES TO | | | INCLUDE COLD WATER PIPE. | | | | | | 3} THE LOAD CALCULATION IS INCORRECT, | | | PLEASE RECALCULATE PER 220.3. | | | | | | 4} THE OVEN CALCULATION MUST COMPLY WITH | | | 220.19, (8 KW MIN). | | | | | | 5} THE NEUTRAL CALCULATION IS INCORRECT | | | PER 220.22, SEE REVIEWED SET OF PLANS. | | | | | | 6} THE AMPERAGE FOR ON THE PANEL | | | SCHEDULE FOR THE AHU AND THE CU. DO NOT | | | CORRELATE WITH THE MECHANICAL PLANS, | | | PLEASE REVISE. | | | | | | 7} A RECEPTACLE MUST BE ADDED AT THE CU | | | PER 210.63. | | | | | | 8} A SMOKE DETECTOR MUST BE ADDED IN | | | "CLOSE PROXIMITY" OF THE STAIRWELL PER | | | NFPA-72, AND 905.2.2 FBC. | | | | | | 9} THE SMOKE DETECTOR NEAR THE UPPER | | | BATH #2 MUST BE A MINIMUM OF 3' AWAY | | | FROM THE DOOR PER 8-1.4.2 NFPA-72. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|