| Plan Review Notes For Permit 04031082 |
| Permit Number |
04031082 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-04-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | A) FROM PREVIOUS REVIEW: THE COMMENT | | | NUMBER SHALL REMAIN THE SAME TO AVOID | | | CONFUSION. | | | 3) UPON FURTHER REVIEW, NOW UNDERSTAND- | | | ING THAT THIS A MEDICAL BUILDING, THE | | | RPZ BACKFLOW IS NOT REQUIRED FOR THE | | | WATER SERVICE. - SECTION 608.3-ALL | | | DEVICES, APPURTENANCES, APPLIANCES AND | | | APPARATUS INTENDED TO SERV SOME SPECIAL | | | FUNCTION, SUCH AS STERILIZATION, DISTILL | | | ATION, PROCESSING, COOLING, ECT SHALL BE | | | PROVIDED WITH BACKFLOW PROTECTION. FILT- | | | ERS SHALL BE PROTECTED AGAINST CONTAMIN- | | | ATION. INDICATE ON PLANS OR PUT NOTE ON | | | PLANS FOR THIS REQUIREMENT. (SEE COMPRE- | | | SSOR ECT.) | | | 5) BACKFLOW PROTECTION NOT SHOWN FOR THE | | | COMPRESSOR. SEE PREVIOUS COMMENT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|