| Plan Review Notes For Permit 04031079 |
| Permit Number |
04031079 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-23 00:00:00 | PROVISO: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 2.TRANSFER AIR GRILLES INDICATED ON | | | THE PLAN ARE NOT PER THE REVISED 2001 | | | FBC(M) 601.4 EXCEPTION #2, 50 SQ INCHES | | | OF GRILLE AREA TO 100 CFM OF SUPPLY AIR. | | | 10" X 10" = 100 SQ IN.PLEASE INCREASE | | | TRANSFER GRILLE SIZE TO COMPLY WITH | | | CODE REQUIREMENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|