| Plan Review Notes For Permit 04031071 |
| Permit Number |
04031071 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-06 00:00:00 | DENIED: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL FOR | | | THE NEW C.U. STAND, SHALL COMPLY WITH | | | 2001 FBC 1511.7 FOR THE HEIGHT | | | REQUIREMENT ABOVE THE FINISHED ROOF. | | | (SEE ATTACHED). | | | | | | 3.PLEASE SUBMIT OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|