2004-04-06 00:00:00DENIED:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 2.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE NEW C.U. STAND, SHALL COMPLY WITH
 2001 FBC 1511.7 FOR THE HEIGHT
 REQUIREMENT ABOVE THE FINISHED ROOF.
 (SEE ATTACHED).
  
 3.PLEASE SUBMIT OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.